4.6 Basic iQpump Setup and Application Preset Parameters
0 to 10 V
2 k
Figure 4.25 Setting the Frequency Reference as a Voltage Signal at Terminal A1
Current Input
Input terminals, A1, A2, and A3 can accept a current input signal. Refer to
current input.
Table 4.18 Analog Input Settings for Frequency Reference Using a Current Signal
Signal
Terminal
Level
4 to 20 mA
A2
0 to 20 mA
Figure 4.26 Setting the Frequency Reference as a Current Signal to Terminal A2
Switching between Main/Auxiliary Frequency References
The frequency reference input can be switched between the analog terminals A1, A2, and A3 using multi-speed inputs. To
use several speed references for a multi-step speed sequence, set the H1-oo parameters to 3, 4, 5, and 32. To assign the Jog
reference to a digital input, set H1-oo to 6.
Setting 2: Serial Communications
This setting requires entering the frequency reference via the RS-485/422 serial communications port (control terminals R+,
R-, S+, S-).
To setup the drive to receive the "Auto Setpoint" from serial communication, set b1-01 to "2: Serial Com," and connect the
RS-422/RS-485 serial communications cable to terminals R+, R-, S+, and S- on the control I/O terminal block. Refer to
153
to see the connection diagram using a PC to provide the auto setpoint reference to the drive.
152
Drive
+V 10.5 V, 20 mA power supply
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
Parameter Settings
Signal Level
Function
Selection
Selection
H3-09 = 2
H3-10 = 0
(Frequency Bias)
H3-09 = 3
Jumper S1
A1/A2/A3
Voltage/Current
Selection
A1 A2 A3
0 or 4 to 20 mA
+10 V
4 k
Customer
+/- 10 V
Supply
OR
0 V
Common
Table 4.18
Gain
H3-11
Drive
V
I
+V 10.5 V, 20 mA power supply
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Drive
+V 10.5 V, 20 mA power supply
0 to 10 V
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
for an example to set terminal A2 for
Bias
Make sure to set jumper S1 on the
H3-12
terminal board to "I" for current
input.
Notes