S6: Protection - YASKAWA iQpump1000 Quick Start Manual

Ac drive
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

B.13 S: Special Application
No.
(Addr.
Name
Hex)
S3-17
(322A) Secondary PI Feedback
Detection Selection
<1> Unit is determined by S3-04.
<2> Upper limit is S3-02, decimal placeholder is determined by S3-03.
u

S6: Protection

No.
(Addr.
Name
Hex)
S6-01
Emergency Override
(3236)
Speed
S6-02
Emergency Override
(3237)
Reference Selection
Output Phase Loss
S6-07
Level for Dynamic
(323C)
Noise Control
324
LCD Display
Selects when secondary PI controller low and high feedback
PI2 FB Det Sel
detection are active.
0: PI2 Enabled
0: Secondary PI enabled
1: Always
1: Always
LCD Display
Sets the speed command used in emergency override mode
E Override Speed
when S6-02 = 0.
E OverrideRefSel
Selects the emergency override speed source.
0: Use S6-01 Ref
0: Use S6-01 Reference
1: Use Freq Ref
1: Use Frequency Reference
Reduces the output phase loss level when Dynamic Noise
DNC Outp Ph Loss
Control is active.
Description
Description
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Values
Page
Default: 0
Range: 0, 1
Values
Page
Default: 0.00 Hz
Min.: 0.00
Max.: 240.00
Default: 0
Range: 0, 1
Default: 100.0%
Min.: 10.0
Max.: 100.0

Hide quick links: