Command Code: 10H, Continuous Writing; Data Address Definition - IMO HD2 IP Series Instruction Manual

Ip55 high ingress protection
Table of Contents

Advertisement

HD2 IP55 High-ingress Protection Series Inverter

9.4.4 Command code: 10H, continuous writing

The command code 10H is used by the master to write data to the inverter. The quantity of data
to be written is determined by "Data quantity", and a maximum of 16 pieces of data can be
written.
For example, to write 5000 (1388H) and 50 (0032H) respectively to 0004H and 0005H of the
inverter whose slave address is 02H, the structure of the frame is described in the following
table.
RTU master command (transmitted by the master to the inverter)
MSB of data writing address
LSB of data writing address
MSB of data quantity
LSB of data quantity
MSB of data to be written to 0004H
LSB of data to be written to 0004H
MSB of data to be written to 0005H
LSB of data to be written to 0005H
RTU slave response (transmitted by the inverter to the master)
MSB of data writing address
LSB of data writing address
MSB of data quantity
LSB of data quantity

9.4.5 Data address definition

This section describes the address definition of communication data. The addresses are used
for controlling the running, obtaining the state information, and setting related function
parameters of the inverter.
9.4.5.1 Function code address representation rules
The address of a function code consists of two bytes, with the MSB on the left and LSB on the
right. The MSB ranges from 00 to ffH, and the LSB also ranges from 00 to ffH. The MSB is the
hexadecimal form of the group number before the dot mark, and LSB is that of the number
behind the dot mark. Take P05.06 as an example, the group number is 05, that is, the MSB of
the parameter address is the hexadecimal form of 05; and the number behind the dot mark is
06, that is, the LSB is the hexadecimal form of 06. Therefore, the function code address is
START
ADDR
CMD
Number of bytes
LSB of CRC
MSB of CRC
END
START
ADDR
CMD
LSB of CRC
MSB of CRC
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
T1-T2-T3-T4 (transmission time of 3.5 bytes)
T1-T2-T3-T4 (transmission time of 3.5 bytes)
T1-T2-T3-T4 (transmission time of 3.5 bytes)
-270
02H
10H
00H
04H
00H
02H
04H
13H
88H
00H
32H
C5H
6EH
02H
10H
00H
04H
00H
02H
C5H
6EH