P00 Group--Basic Functions - IMO HD2 IP Series Instruction Manual

Ip55 high ingress protection
Table of Contents

Advertisement

HD2 IP55 High-ingress Protection Series
Function
code
Speed control
P00.00
P00.01
command
Communicati
on running
P00.02
command
Max. output
P00.03
frequency
Upper limit of
P00.04
frequency
Lower limit of
P00.05
frequency
A frequency
P00.06
command
B frequency
P00.07
command
P00 group––Basic functions
Name
0: SVC 0
1: SVC 1
2: SVM
mode
3: VC
Note: If 0, 1 or 3 is selected, it is required to
carry out motor parameter autotuning first.
Running
0: Keypad
1: Terminal
Source
2: Communication
0: Modbus
1: PROFIBUS/CANopen/DeviceNet
2: Ethernet
3: EtherCAT/PROFINET
4: PLC programmable card
channel
5: Wireless communication card
Note: 1, 2, 3, 4 and 5 are extended functions
which are applicable with corresponding cards.
Used to set the max. output frequency of the
inverter. It is the basis of frequency setup and the
acceleration/deceleration.
Setting range: Max (P00.04, 10.00) –630.00Hz
The upper limit of running frequency is upper limit
value of inverter output frequency. This value
should be no more than the max. output
frequency.
running
When the set frequency is higher than the upper
limit frequency, the inverter runs at the upper limit
frequency.
Setting range:
frequency)
The lower limit of running frequency is the lower
limit value of inverter output frequency.
When the set frequency is lower than the lower
limit frequency, the inverter runs at the lower limit
frequency.
running
Note: Max. output frequency ≥ upper limit
frequency ≥ lower limit frequency.
Setting range:
running frequency)
0: Set via keypad
1: Set via AI1
selection
2: Set via AI2
3: Set via AI3
4: Set via high speed pulse HDIA
selection
5: Set via simple PLC program
Description
P00.05–P00.03
(max. output
0.00Hz–P00.04
(upper limit of
-115-
Function parameter list
Default
Modify
value
2
0
0
50.00Hz
50.00Hz
0.00Hz
0
15