Appendix B Technical Data; What This Chapter Contains; Derated Application; Capacity - IMO HD2 IP Series Instruction Manual

Ip55 high ingress protection
Table of Contents

Advertisement

HD2 IP55 High-ingress Protection Series Inverter
B.1 What this chapter contains
This chapter describes the technical data of the inverter and its compliance to CE and other
quality certification systems.
B.2 Derated application
B.2.1 Capacity
Choose a inverter based on the rated current and power of the motor. To endure the rated
power of the motor, the rated output current of the inverter must be larger or equal to the rated
current of the motor. The rated power of the inverter must be higher or equal to that of the motor.
Note:
1. The maximum allowable shaft power of the motor is limited to 1.5 times the rated power of
the motor. If the limit is exceeded, the inverter automatically restricts the torque and current
of the motor. This function effectively protects the input shaft against overload.
2. The rated capacity is the capacity at the ambient temperature of 40°C.
3. You need to check and ensure that the power flowing through the common DC connection in
the common DC system does not exceed the rated power of the motor.
B.2.2 Derating
If the ambient temperature on the site where the inverter is installed exceeds 40°C, the altitude
exceeds 1000 m, the heat emission hole cover plate is used, or the carrier frequency is greater
than the recommended frequency in the manual (see function code P00.14 for the
recommended frequency), the inverter needs to be derated.
B.2.2.1 Derating due to temperature
When the temperature ranges from +40°C to +50°C, the rated output current is derated by 1%
for each increased 1°C. For the actual derating, see the following figure.
Note: It is not recommended to use the inverter at a temperature higher than 50°C. If you do,
you shall be held accountable for the consequences caused.

Appendix B Technical data

Figure B-1 Diagram of actual temperature derating
Derating coefficient (%)
100
90
80
60
40
20
-10
0
10
20
Temperature (℃)
30
40
50
-314

Advertisement

Table of Contents
loading