Installation Direction - IMO HD2 IP Series Instruction Manual

Ip55 high ingress protection
Table of Contents

Advertisement

HD2 IP55 High-ingress Protection Series
Environment
Running
environment
Altitude
Vibration
Installation
direction
Note: inverters must be installed in ventilated environments free of corrosive gases and
conductive dust.

4.2.2 Installation direction

The inverter can be installed on the wall or in a cabinet.
The inverter must be installed vertically. Check the installation position according to
following requirements. See Appendix C "Dimension drawings" for detailed outline dimensions.
OK
a. Vertical installation
The installation site should meet the following requirements.
Away from electromagnetic radiation sources;
Away from oil mist, corrosive gases and combustible gases;
Ensure foreign object like metal powder will not fall into the inverter (do
not install the inverter onto combustible object like wood);
Away from radioactive substance and combustible objects;
Away from corrosive liquid;
Low salt content;
No direct sunlight
Below 1000m;
When the installation site altitude exceeds 1000m, derate 1% for every
increase of 100m; when the installation site altitude exceeds
3000m, consult the local IMO dealer or office.
Up to 5.8m/s
2
(0.6g)
Install the inverter vertically to ensure good heat dissipation effect.
Figure 4-1 Installation direction of the inverter
b.Horizontal installation
Condition
NO
-14-
Installation Guide
NO
c.Transverse installation