4.1.3 Preparation before running the motor for a test--Setting function code data

Before starting running the motor, set function code data specified in Table 4.1 to the motor ratings
and your system design values. For the motor, check the rated values printed on the nameplate of
the motor. For your system design values, ask system designers about them.
For details about how to change function code data, refer to Chapter 3, Section 3.4 "Setting
the Function Codes." If the motor capacity is different from the inverter capacity, refer to
Chapter 5, function code H03.
Table 4.1 Settings of Function Code Data before Driving the Motor for a Test
Function code
Name
F 04
Base frequency
Rated Voltage (at base
F 05
frequency)
Motor Parameter
P 02
(Rated capacity)
Motor Parameter
P 03
(Rated current)
P 99
Motor Selection
F 03
Maximum frequency
F 07
Acceleration time 1*
F 08
Deceleration time 1*
(Note) Values in parentheses ( ) in the above table denote default settings for the EU version except three-phase
200 V series.
Function code data
60.0 (50.0) (Hz)
0 (V)
(Output voltage interlocked
with the source voltage)
Applicable motor rated
Motor ratings (printed on the
capacity
nameplate of the motor)
Rated current of applicable
motor
0: Characteristic of motor,
0 (standard 8-series
motors)
System design values
60.0 (50.0) (Hz)
* For a test-driving of the motor,
increase values so that they
are longer than your system
6.00 (sec)
design values. If the set time
is short, the inverter may not
6.00 (sec)
start running the motor.
4-2
Factory setting
(Note)
(Note)