P06 Group--Output Terminals - IMO HD2 IP Series Instruction Manual

Ip55 high ingress protection
Table of Contents

Advertisement

HD2 IP55 High-ingress Protection Series Inverter
Function
code
Lower limit
P05.45
frequency of
Correspondin
g setting of
P05.46
lower limit
frequency of
Upper limit
P05.47
frequency of
Correspondin
g setting of
P05.48
upper limit
frequency of
frequency
P05.49
input filter
P05.50
signal type
P05.51–
Reserved
P05.52
Function
code
HDO output
P06.00
P06.01
HDO output
P06.02
P06.03
output selection
P06.04
output selection
Name
0.000
kHz–P05.47
HDIB
-300.0%–300.0%
HDIB
P05.45–50.000kHz
HDIB
-300.0%–300.0%
HDIB
HDIB
0.000s–10.000s
time
0–1
0: Voltage type
AI1 input
1: Current type
Note: You can set the AI1 input signal type
through the corresponding function code.
/
P06 group––Output terminals
Name
0: Open collector high-speed pulse output:
Max. frequency of the pulse is 50.00kHz. For
details about the related functions, see
type
P06.27–P06.31.
1: Open collector output: For details about the
related functions, see P06.02.
Y output
0: Invalid
selection
1: In running
2: In forward running
selection
3: In reverse running
4: In jogging
Relay RO1
5: inverter fault
6: Frequency level detection FDT1
Relay RO2
7: Frequency level detection FDT2
8: Frequency reached
Description
Description
-148
Function parameter list
Default
Modify
value
0.000
kHz
0.0%
50.000
kHz
100.0%
0.030s
0
/
/
Default
Modify
value
0
0
0
1
5