Reactors - IMO HD2 IP Series Instruction Manual

Ip55 high ingress protection
Table of Contents

Advertisement

HD2 IP55 High-ingress Protection Series
inverter model
HD2IP-9.5A-43
HD2IP-14A-43
HD2IP-18.5A-43
HD2IP-25A-43
HD2IP-32A-43
HD2IP-38A-43
HD2IP-45A-43
HD2IP-60A-43
HD2IP-75A-43
HD2IP-92A-43
HD2IP-115A-43
HD2IP-150A-43
HD2IP-180A-43
HD2IP-215A-43
Note: Parameters of the optional accessories described in the preceding table are ideal values.
You can select accessories based on the actual market conditions but try not to use those with
lower values.
D.6 Reactors
When the voltage of the grid is high, the transient large current that flows into the input power
circuit may damage rectifier components. You need to configure an AC reactor on the input
side, which can also improve the current adjustment coefficient on the input side.
When the distance between the inverter and motor is longer than 50 m, the parasitic
capacitance between the long cable and ground may cause large leakage current, and
overcurrent protection of the inverter may be frequently triggered. To prevent this from
happening and avoid damage to the motor insulator, compensation must be made by adding
an output reactor. When a inverter is used to drive multiple motors, take the total length of the
motor cables (that is, sum of the lengths of the motor cables) into account. When the total length
is longer than 50 m, an output reactor must be added on the output side of the inverter. If the
distance between the inverter and motor is 50 m to 100 m, select the reactor according to the
following table. If the distance is longer than 100 m, contact IMO's technical support technicians.
Table D-4 Parameters of the optional accessories
Breaker rated
current (A)
20
25
32
50
63
63
80
100
125
140
180
225
250
315
Fast-acting fuse
rated current (A)
20
35
40
50
60
70
90
125
125
150
200
250
300
350
-329-
Contactor rated current
(A)
18
25
32
38
50
65
80
80
98
115
150
185
225
265