9.1 What this chapter contains

This chapter describes the communication protocol of HD2 IP55 high protection high-
ingress protectionGoodrive350 series products.
HD2 IP55 high protection high-ingress protection HD2 series inverters provide RS485
communication interfaces and adopt the master-slave communication based on the
international standard Modbus communication protocol. You can implement centralized control
(setting commands for controlling the inverter, modifying the running frequency and related
function code parameters, and monitoring the working state and fault information of the inverter)
through PC/PLC, upper control computer, or other devices to meet specific application
requirements.

9.2 Modbus protocol introduction

Modbus is a software protocol, a common language used in electronic controllers. By using this
protocol, a controller can communicate with other devices through transmission lines. It is a
general industrial standard. With this standard, control devices produced by different
manufacturers can be connected to form an industrial network and be monitored in a centralized
way.
The Modbus protocol provides two transmission modes, namely American Standard Code for
Information Interchange (ASCII) and remote terminal units (RTU). On one Modbus network, all
the device transmission modes, baud rates, data bits, check bits, end bits, and other basic
parameters must be set consistently.
A Modbus network is a control network with one master and multiple slaves, that is, on one
Modbus network, there is only one device serving as the master, and other devices are the
slaves. The master can communicate with one slave or broadcast messages to all the slaves.
For separate access commands, a slave needs to return a response. For broadcasted
information, slaves do not need to return responses.

9.3 Application of Modbus

HD2 IP55 high-ingress protection series inverters use the RTU mode provided by the
Modbus protocol, and RS485 interfaces are used.

9.3.1 RS485

RS485 interfaces work in half-duplex mode and transmit data signals in the differential
transmission way, which is also referred to as balanced transmission. An RS485 interface uses
a twisted pair, where one wire is defined as A (+), and the other B (-). Generally, if the positive
electrical level between the transmission drives A and B ranges from +2 V to +6 V, the logic is
"1"; and if it ranges from -2 V to -6 V, the logic is "0".
The 485+ terminal on the terminal block of the inverter corresponds to A, and 485- corresponds
to B.
The communication baud rate (P14.01) indicates the number of bits transmitted in a second,
and the unit is bit/s (bps). A higher baud rate indicates faster transmission and poorer anti-
interference capability. When a twisted pair of 0.56 mm (24 AWG) is used, the maximum
transmission distance varies according to the baud rate, as described in the following table.

9 Communication protocol

-261-
Communication protocol