HD2 IP55 High-ingress Protection Series Inverter
Function
code
P05.12
P05.13
P05.14
P05.15
P05.16
P05.17
P05.18
P05.19
P05.20
HDIA terminal switch-on delay 0.000–50.000s
P05.21
HDIA terminal switch-off delay 0.000–50.000s
P05.22
HDIB terminal switch-on delay 0.000–50.000s
P05.23
HDIB terminal switch-off delay 0.000–50.000s
P07.39
P17.12

5.5.12 Digital output

The HD2 IP55 series inverter carries two groups of relay output terminals, one open collector Y
output terminal and one high-speed pulse output (HDO) terminal. The function of all the digital
output terminals can be programmed by function codes, of which the high-speed pulse output
terminal HDO can also be set to high-speed pulse output or digital output by function code.
The table below lists the options for the above four function parameters, and users are allowed
to select the same output terminal functions repetitively.
Set
value
0
Name
S1 terminal switch-on delay
S1 terminal switch-off delay
S2 terminal switch-on delay
S2 terminal switch-off delay
S3 terminal switch-on delay
S3 terminal switch-off delay
S4 terminal switch-on delay
S4 terminal switch-off delay
Input terminal state of present
fault
Digital input terminal state
Function
Invalid
Description
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
/
/
Output terminal has no function
-90-
P06.05, P17.12, P07.40 display
Y
BIT0
ROI
BIT2
0: Open collector high-
P06.00
speed pulse output
1: Open collector output
Description
Default
value
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0
0
HDO
BIT1
RO2
BIT3