9-4-9 Communication Error Code

The inverter detects the following errors.
The error code is in hexadecimal notation.
Error code
Name of error
(hexadecimal)
47H
Checksum error
48H
Parity error
49H
Others
4AH
Format error
4BH
Command error
4EH
Function code error
4FH
Write disable
50H
Data error
Table 9-4-4 Communication error code
The inverter does not return NAK in response to
errors 47 through 49 above. It issues no
response.
In the case of errors 4A through 50, an NAK
response with an NAK code in the response
character field and the two digit hexadecimal
error code in the data field is returned.
The latest error can be referred to using the
transmission error end code monitor (M26).

9-4-10 Data Type

(1) In the case of value data
16 bit data is expressed in a hexadecimal
and set using four ASCII codes. Concretely
speaking, the data is between "0000" and
"FFFF".
Decimal fractions are weighted into integers.
Refer to the corresponding section because
the weight varies according to each piece of
function data. In some functions, the
negative value is expressed in two's
complement.
The bit data is converted into the
hexadecimal and expressed.
The acknowledgement sent from the inverter
in response to a selecting (writing) request is
the
writing
data.
acknowledgement,
returned in two hexadecimal characters.
Set "0000" or an arbitrary letters and
numbers in the data to be transmitted to the
inverter in a polling (reading) frame.
Example: Frequency data, weight 100 times
120.00Hz 120Å~100=12000=2EE0H
9-19
Description
The checksum of the frame sent to the own station is in
discrepancy.
The parity is in discrepancy.
Reception error other than above (framing, overrun)
The enquiry character or the end-of-text character in the
transmitted frame is in an incorrect position.
A code other than designated commands (standard and
option) is sent.
A request for an unknown function code is issued.
A write prohibited function or in-operation write prohibited
function is written during operation.
Data exceeding the standard range is written.
In
the
negative
the
error
code
is
The data is "2" in ASCII, "E" in ASCII, "E" in
ASCII and "0" in ASCII in order from the first
character to the fourth character.
Acceleration time data, weight 10 times
6.5 sec: 6.5 x 10 = 65 = 41H
The data is "0" in ASCII, "0" in ASCII, "4" in
ASCII and "1" in ASCII in order from the first
character to the fourth character.
(2) In the case of bit data
For bit type data requested by S06, M13 or
other functions, the bit data is expressed in
hexadecimal notation and each digit is
transmitted in ASCII codes.
Example: S06 with FWD (bit 0) ON, X1 (bit
2) ON, and X3 (bit 4) ON
Bit data = 0000 0000 0001 0101 ¡ 0015H
¡ 30H 30H 31H 35H
(Hexadecimal)
(ASCII)
Specifications

Hide quick links:

Advertisement

Table of Contents
loading