Levelflex FMP51, FMP52, FMP54
Navigation
Description
Option
Factory setting
Fail safe time
Navigation
Description
Range of values
Factory setting
Fail safe type
Navigation
Description
Options
Factory setting
Fail safe value
Navigation
Prerequisite
Description
Range of values
Endress+Hauser
Setup ® Advanced setup ® Digital output 1...4 ® Invert
Allows to invert the digital output signal (i.e. to swap the states "0" and "1").
• Off
• On
Off
Setup ® Advanced setup ® Digital output 1...4 ® Fail safe time
Defines the fail-safe time, i.e. the time which passes after the occurrence of an error until the DO
block assumes the defined error state.
Any positive IEEE floating point number:
0 to 3.4 10
38
s
0
Setup ® Advanced setup ® Digital output 1...4 ® Fail safe type
Defines the output behavior of the DO block in the case of an error.
• Fail safe value
The output assumes the value defined in Fail safe value.
• Fallback value
The output maintains the value it had at the moment the error occurred.
• Off
The output assumes a value according to the current state of the block. The error is ignored.
Fallback value
Setup ® Advanced setup ® Digital output 1...4 ® Fail safe value
Only visible for Fail safe type = Fail safe value
Defines the value the output assumes in the case of an error.
0 to 255