Description of device parameters (operating menu)
Process property
Navigation
Description
Options
Factory setting
Additional information
DC lower medium
Navigation
Description
Input range
132
The "Interface" submenu
This submenu is only visible for "Operating mode" = "Interface".
Setup ® Advanced Setup ® Interface ® Process property
Defines a typical rate of level change
• Fast > 1 m(40")/min
• Standard < 1 m(40")/min
• Medium < 10 cm(4")/min
• Slow < 1 cm(0.4")/min
• No filter
Standard < 1m(40")/min
The device adjusts the signal evaluation filters and the damping of the output signal to
the typical rate of level change defined in this parameter:
For interface measurements
Process property
Fast > 1m(40")/min
Standard < 1 m(40")/min
Medium < 10 cm(4")/min
Slow < 1 cm(0.4")/min
No filter
Setup ® Advanced setup ® Interface ® DC lower medium
Defines the dielectric constant of the lower
medium (DC
)
2
10 ... 100
Levelflex FMP51, FMP52, FMP54
Step response time [s]
5
15
40
74
2.2
DC
2
Endress+Hauser
DC
2
A0013252