Levelflex FMP51, FMP52, FMP54
Fail safe type
Navigation
Description
Options
Factory setting
Fail safe value
Navigation
Prerequisite
Description
Range of values
Factory setting
Out value
Navigation
Description
Out status
Navigation
Description
Endress+Hauser
Setup ® Advanced setup ® Analog output 1...4 ® Fail safe type
Defines the output behavior of the AO block in the case of an error.
• Fail safe value
The output assumes the value defined in Fail safe value.
• Fallback value
The output maintains the value it had at the moment the error occurred.
• Off
The output assumes a value according to the current state of the block. The error is ignored.
Fallback value
Setup ® Advanced setup ® Analog output 1...4 ® Fail safe value
Only visible for Fail safe type = Fail safe value
Defines the value the output assumes in the case of an error.
Any IEEE floating point number:
-3,4 10
38
... + 3,4 10
38
0
Setup ® Advanced setup ® Analog output 1...4 ® Out value
Diagnostics ® Measured value ® Analog output 1...4 ® Out value
Displays the current output value of the block.
Setup ® Advanced setup ® Analog output 1...4 ® Out status
Diagnostics ® Measured value ® Analog output 1...4 ® Out status
Displays the current status of the output value of the block.
Description of device parameters (operating menu)
157