4.7.4.14.3.2 Serial interface COM - Pinout
Serial interface COM is available in the IF option 2 add-on slot.
Variant
Type
UART
Galvanic isolation
Transfer rate
Bus length
Pin
1
2
3
4
5
6
7
8
9
10
1)
The interfaces, etc. available on the device or module have been numbered for the purpose of clear differentiation. This numbering may deviate from the
numbering used by the respective operating system, however.
2)
This interface can only be used in Automation Runtime and is displayed as IF5 in Automation Studio / Automation Runtime. It is not a "PC interface" and
therefore not displayed in BIOS.
Cable data
For more detailed information about the transfer rate, bus length or cable requirements for the respective inter-
faces/buses, see
"Cable data" on page
4.7.4.14.3.3 CAN bus interface - Pinout
The CAN bus interface is available in the IF option 2 add-on slot.
Variant
Galvanic isolation
Transfer rate
Bus length
Pin
1
2
3
4
5
6
7
8
9
10
1)
The interfaces, etc. available on the device or module have been numbered for the purpose of clear differentiation. This numbering may deviate from the
numbering used by the respective operating system, however.
2)
This interface can only be used in Automation Runtime and is displayed as IF3 in Automation Studio / Automation Runtime. It is not a "PC interface" and
therefore not displayed in BIOS.
CAN driver setting
The baud rate can be set either with predefined values or via the bit timing register. For additional information,
see Automation Help.
Bit timing register 1
00h
80h or 00h
81h or 01h
83h or 03h
84h or 04h
89h or 09h
Automation PC 3100 User's manual V 2.10
Serial interface COM
RS232
10-pin, male
RS232, not modem supported
16550-compatible,
16-byte FIFO buffer
No
Max. 115 kbit/s
Max. 15 m
Pinout
-
Shield
-
-
-
-
-
COM GND
RXD
TXD
245.
CAN bus
1)2)
10-pin, male
Yes
Max. 1 Mbit/s
Max. 1000 m
Pinout
-
Shield
-
-
CAN H
CAN L
CAN GND
-
-
-
Bit timing register 0
14h
1Ch
1Ch
1Ch
1Ch
1Ch
1)2)
1
3
5
2
4
6
1
3
5
2
4
6
Technical data
7
9
8 10
7
9
8 10
Baud rate
1000 kbit/s
500 kbit/s
250 kbit/s
125 kbit/s
100 kbit/s
50 kbit/s