Power Panel C80
User's manual
Version: 1.02 (April 2021)
Order no.: MAPPC80-EN
Translation of the original documentation

Advertisement

Table of Contents
loading

Summary of Contents for B&R Power Panel C80

  • Page 1 Power Panel C80 User's manual Version: 1.02 (April 2021) Order no.: MAPPC80-EN Translation of the original documentation...
  • Page 2 Publishing information B&R Industrial Automation GmbH B&R Strasse 1 5142 Eggelsberg Austria Telephone: +43 7748 6586-0 Fax: +43 7748 6586-26 office@br-automation.com Disclaimer All information in this manual is current as of its creation. The contents of this manual are subject to change without notice.
  • Page 3: Table Of Contents

    4.6.3 Derating the ambient temperature......................28 4.7 Device interfaces and slots...........................29 4.7.1 Interface overview........................... 29 4.7.2 Power supply............................29 4.7.3 Grounding..............................30 4.7.4 USB interfaces............................30 4.7.5 LED status indicators..........................31 4.7.6 Fieldbus interfaces..........................32 Power Panel C80 User's manual V1.02...
  • Page 4 6.8.3 Boot animation............................63 7 Commissioning......................64 7.1 Basic information............................64 7.2 Calibration..............................64 7.3 Operating the Power Panel.......................... 64 7.3.1 Keyboard..............................64 7.3.2 Mouse..............................64 8 Maintenance......................65 8.1 Changing the battery............................ 65 8.2 Cleaning................................ 67 8.3 Pixel errors..............................67 Power Panel C80 User's manual V1.02...
  • Page 5 10 International and national certifications.............72 10.1 Directives and declarations.........................72 10.1.1 CE marking............................72 10.1.2 EMC Directive............................72 10.2 Certifications..............................73 10.2.1 UL certification............................73 10.2.2 EAC................................73 10.2.3 KC................................73 10.2.4 RCM...............................73 11 Environmentally friendly disposal...............74 11.1 Separation of materials..........................74 Power Panel C80 User's manual V1.02...
  • Page 6: Introduction

    Up to 6 mm ±0.1 mm Over 6 to 30 mm ±0.2 mm Over 30 to 120 mm ±0.3 mm Over 120 to 400 mm ±0.5 mm Over 400 to 1000 mm ±0.8 mm Power Panel C80 User's manual V1.02...
  • Page 7: General Safety Guidelines

    Electronic devices are generally not failsafe. If the programmable logic controller, operating or control device or uninterruptible power supply fails, the user is responsible for ensuring that connected devices (such as motors) are brought to a safe state. Power Panel C80 User's manual V1.02...
  • Page 8: Transport And Storage

    Automation Panels or Power Panels are protected on the front against the ingress of dust and moisture when installed correctly (e.g. cutout installation). The back of all devices must be protected against the ingress of dust and moisture, however, or the dust deposits must be removed at suitable intervals. Power Panel C80 User's manual V1.02...
  • Page 9: Programs, Viruses And Malicious Programs

    The term "control systems" refers to all types of B&R products such as controllers (e.g. X20), HMI systems (e.g. Power Panel T30), process control systems (e.g. APROL) and supporting systems such as engineering workstations with Automation Studio. Power Panel C80 User's manual V1.02...
  • Page 10: System Overview

    Seq. number: C[0...Z][0...Z][0...Z] Examples Power Panel C80, glass front, controller with mapp View HMI unit, fieldbus interfaces: 2x CAN bus. CPU and memory of the controller: 1600 MHz (Intel Atom E3940), 4 GB DRAM, 32 kB FRAM, 4 GB onboard flash drive.
  • Page 11: System Characteristics

    Connector 300 VDC - 10-pin female - Cage clamp terminal block - Protected against vibration by the screw flange 0TB6102.3000-00 2-pin accessory screw clamp terminal block (3.81) 0TB6102.3100-00 Accessory 2-pin cage clamp terminal block (3.81) Power Panel C80 User's manual V1.02...
  • Page 12: Device Description

    Accessory plate Plate for securing / strain relief of the connection lines and connecting the shield 4.1.2 Optional accessories Order number Description 0TB6102.3000-00 Accessory terminal block, 2-pin (3.81), screw clamp terminal block, 1.5 mm² Power Panel C80 User's manual V1.02...
  • Page 13: Technical Data

    ACPI 5.0 Interfaces Interface IF1 Fieldbus POWERLINK V2 managing or controlled node Type Type 4 Variant 1x RJ45 shielded Line length Max. 100 m between 2 nodes (segment length) Max. transfer rate 100 Mbit/s Power Panel C80 User's manual V1.02...
  • Page 14 4PPC80.0573-10B 0xE9EC 4PPC80.0573-11A 0xA408 4PPC80.0573-11B 0xA415 4PPC80.0573-12A 0xA416 4PPC80.0573-12B 0xA417 4PPC80.0573-13A 0xA418 4PPC80.0573-13B 0xA419 4PPC80.0702-10A 0xF9D8 4PPC80.0702-10B 0xF9D5 4PPC80.0702-11A 0xA41A 4PPC80.0702-11B 0xA41B 4PPC80.0702-12A 0xF9D9 4PPC80.0702-12B 0xF9D6 4PPC80.0702-13A 0xF9DA 4PPC80.0702-13B 0xF9D7 4PPC80.101E-10A 0xF9DE 4PPC80.101E-10B 0xF9DB Power Panel C80 User's manual V1.02...
  • Page 15: Specific Technical Data Of The Display Variants

    At 25°C ambient temperature. Reducing the brightness by 50% can typically result in an approximately 50% increase in the half-brightness time. Can be set via software. IEC 61010-2-201 requirements must be observed. Power consumption including all interfaces. The internal fuse cannot be replaced by the user or reset. Power Panel C80 User's manual V1.02...
  • Page 16: Technical Data Of The Interface Variants

    3 pins of the 10-pin multipoint connector Transfer rate Max. 115.2 kbit/s IF10: RS485 interface Order number 4PPC80.xxxx-x3x Interfaces Interface IF10 Type RS485 Variant 3 pins of the 10-pin multipoint connector Transfer rate Max. 115.2 kbit/s Power Panel C80 User's manual V1.02...
  • Page 17: Technical Information

    • Display size and resolution • Display orientation This means: Power Panel C80 variants can be replaced by each other if they differ only by the device color (coating) or glass variant (anti-glare / not anti-glare, glass print, front panel overlays).
  • Page 18: Viewing Angles

    Hydrogen chloride 6% • Coffee • Stamping ink • Coca-Cola • • • Diesel • • Lysol Turpentine • Diesel oil • • Methylbenzene Turpentine oil replacement (thinner) • Dimethylbenzene • • Methyl ethyl ketone Trichloroethylene Power Panel C80 User's manual V1.02...
  • Page 19: Temperature/Humidity Diagrams

    RH [%] Relative humidity (RH) in percent and non-condensing 7.0" variants RH [%] T [°C] Diagram legend Operation T [°C] Temperature in °C Storage and transport RH [%] Relative humidity (RH) in percent and non-condensing Power Panel C80 User's manual V1.02...
  • Page 20 RH [%] Relative humidity (RH) in percent and non-condensing 12.1" variants RH [%] T [°C] Diagram legend Operation T [°C] Temperature in °C RH [%] Relative humidity (RH) in percent and non-condensing Storage and transport Power Panel C80 User's manual V1.02...
  • Page 21 Device description 15.6" variants RH [%] T [°C] Diagram legend Operation T [°C] Temperature in °C Storage and transport RH [%] Relative humidity (RH) in percent and non-condensing Power Panel C80 User's manual V1.02...
  • Page 22: Dimensions

    4.5 Dimensions Information: All specifications in dimension diagrams and associated tables are in millimeters [mm]. 2D and 3D diagrams (DXF and STEP formats) can be downloaded from the B&R website (www.br-automation.com). 4.5.1 5.7" variants Power Panel C80 User's manual V1.02...
  • Page 23: Variants

    Device description 4.5.2 7.0" variants 208.4 166.4 35.5 Power Panel C80 User's manual V1.02...
  • Page 24: Variants

    Device description 4.5.3 10.1" variants Power Panel C80 User's manual V1.02...
  • Page 25: Variants

    Device description 4.5.4 12.1" variants 323.6 37.5 Power Panel C80 User's manual V1.02...
  • Page 26: Variants

    Device description 4.5.5 15.6" variants 37.5 Power Panel C80 User's manual V1.02...
  • Page 27: Environmental Properties

    If the specified spacing for air circulation cannot be maintained, the maximum specified temperatures of the temperature sensors (see "Temperature sensor positions" on page 28) must be monitored in the application and appropriate measures taken if these values are exceeded. Power Panel C80 User's manual V1.02...
  • Page 28: Temperature Sensor Positions

    If one or more of the above conditions apply, the device is permitted to be derated up to the maximum operating temperature (see ambient conditions in the technical data) minus the specified derating temperatures. If several conditions apply, the individual derating values must be added together. Power Panel C80 User's manual V1.02...
  • Page 29: Device Interfaces And Slots

    Male Electrical properties Nominal voltage 24 VDC ±25%, SELV/PELV Overvoltage category per EN 61131-2 Inrush current Typ. 5 A, max. 100 A for < 50 μs Galvanic isolation IEC 61010-2-201 requirements must be observed. Power Panel C80 User's manual V1.02...
  • Page 30: Grounding

    USB storage medium (e.g. flash drive) Terminal USB storage medium with system image for updating the terminal system (see "Update " on page 52). USB keyboard USB mouse USB keyboard and/or USB mouse are automatically recognized by the terminal. Power Panel C80 User's manual V1.02...
  • Page 31: Led Status Indicators

    Terminating resistor not switched on. IF7: CAN bus Terminating resistor switched on. OPS4 Yellow TxD/RxD: Data is being transmitted or received. OPS5 Yellow Terminating resistor not switched on. IF8: CAN bus Terminating resistor switched on. Power Panel C80 User's manual V1.02...
  • Page 32: Fieldbus Interfaces

    Bus length up to 1000 m: 50 kbit/s RS232 115.2 kbit/s RS485 115.2 kbit/s 4.7.7 Reset button The device is set to mode SERVICE mode with the reset button by default. This setting can be changed in Au- tomation Studio. Power Panel C80 User's manual V1.02...
  • Page 33: Ethernet Interface (If2)

    In this mode, the interface is operated as an Ethernet interface. The INA2000 station number is set using the B&R Automation Studio software. Information: If interface IF1 is operated in Ethernet mode, then this interface receives its own IP address and works independently of Ethernet interface IF2. Power Panel C80 User's manual V1.02...
  • Page 34: Battery

    Data is retained by a capacitor in order to avoid data loss during battery replacement. Information: The self-discharge time when changing the battery is approx. 2 minutes. At 50°C, 8.5 μA for the components being supplied and self-discharge of 40%). Power Panel C80 User's manual V1.02...
  • Page 35: Product Information

    Valid test and conformity ID for the product, see section "Technical data" on page 13 Safety notices, warnings and information about the product License adhesive label for operating systems (configuration-dependent) Space for individual customer information (configuration-dependent) Power Panel C80 User's manual V1.02...
  • Page 36: Installation And Wiring

    Information about the device's environment • Observe the notes and regulations regarding the power supply and functional ground. • Observer the specified bend radius when connecting cables. • Ventilation openings are not permitted to be covered or blocked. Power Panel C80 User's manual V1.02...
  • Page 37: Requirements For The Installation Cutout

    The device must ultimately be installed in a protective housing with sufficient rigidity (per UL 61010-1 and UL 61010-2-201). 5.2.1 Installation cutout Information: When installing, spacing for air circulation and additional free space for operating and servicing the device must be taken into account. Power Panel C80 User's manual V1.02...
  • Page 38 A derating of the ambient temperature of 5°C must be taken into account for all mounting orientations and diagonals starting at a wall thickness greater than 4 mm (see "Derating the ambient temperature" on page 28). Information: A minimum circumferential distance of 30 mm must be maintained in order to enable installation with retaining clips. Power Panel C80 User's manual V1.02...
  • Page 39: Installing With Retaining Clips

    4. Secure the retaining clips to the wall or control cabinet panel by tightening the mounting screws with a flat- blade screwdriver. Figure: Securing the retaining clips Torque limiting is built into the retaining clips. Power Panel C80 User's manual V1.02...
  • Page 40: Installing With A Vesa Bracket

    VESA 100 x 100 VESA 100 x 100 Notice! The following points must be observed to avoid damaging the device: • Select suitable screws (M4) according to the application. • Screw-in depth: Max. 8 mm Power Panel C80 User's manual V1.02...
  • Page 41: Mounting Orientations

    • For the maximum permissible ambient temperature, see the technical data for the respective device. The following drawings show the specified mounting orientations of Power Panel C80 devices. These are only permitted to be installed as specified. During installation, it is important to make sure that the spacing as described in section "Spacing for air circulation"...
  • Page 42: Grounding (Functional Ground)

    Grounding in the control cabinet Figure 3: Grounding in the control cabinet Notice! The ground connection of the device must be low impedance and connected to ground (e.g. grounding rail in the control cabinet) using a short path. Power Panel C80 User's manual V1.02...
  • Page 43: Securing The Connecting Cables

    A central ground connection is available to effectively deflect interference. All cable shields must be con- nected to the grounding plate with good conductivity using cable ties or by other means. Figure 4: (symbolic image) Power Panel C80 User's manual V1.02...
  • Page 44: Requirements For The Cables Used

    Installation and wiring 5.8 Requirements for the cables used Notice! To meet the UL certification requirements, copper cables must be used that are designed for an oper- ating temperature >70°C. Power Panel C80 User's manual V1.02...
  • Page 45: Software

    HMI application depending on the configuration in Automation Studio. System requirements The following minimum software versions are required to run B&R Hypervisor on the Power Panel C80: • ARemb upgrade AR D4.90 • Automation Studio V4.9.3 Information: For details about B&R Hypervisor, see Automation Help.
  • Page 46: Automation Runtime

    Licensing using the Technology Guarding wizard is available starting with Automation Studio V4.1 and Automation Runtime V4.08. A Technology Guard is not necessary in earlier Automation Runtime versions. For additional information about Technology Guarding, see Automation Help. Power Panel C80 User's manual V1.02...
  • Page 47: Configuration In Automation Studio

    6.2.1 Standard options Standard options The standard options for configuring the Power Panel C80 in Automation Studio are described in Automation Help: ➯ Programming / Editors / Configuration editors / Hardware configuration / CPU configuration / SG4 6.2.2 Terminal configuration...
  • Page 48 Input range: 0°, 90°, 180°, 270° (in 90° steps) The angle of rotation of the display is set here. This setting affects how screen content is output. After selection, the display content is rotated clockwise according to the specified angle. Power Panel C80 User's manual V1.02...
  • Page 49 If the screensaver is active after the configured time, the display changes to the selected mode: Selection Description Black Screen The display is dark. The backlight remains on. Backlight off The display is dark. The backlight is switched off (result: lower power consumption). Power Panel C80 User's manual V1.02...
  • Page 50 8081. If the HMI application (mapp View or web server) is provided by the Power Panel C80 controller, localhost can be used as the hostname. This specific hostname is then automatically replaced by the IP address of the controller.
  • Page 51 The background color can be entered in two ways: 1. Hex code: #xxxxxx 2. Color keyword An overview of possible colors can be obtained from the following website: https://www.w3.org/TR/SVG11/type- s.html#ColorKeywords. Examples: Color Hex code Lime green #32CD32 Blue #0000FF Azure #F0FFFF Power Panel C80 User's manual V1.02...
  • Page 52: Nat Configuration

    • Verification of signature PPC80Image.img.gz.sig indicates that the system comes from a trusted source. 6.2.3 NAT configuration The settings under "NAT configuration" can be used to set the access rights of and on the Power Panel C80. Power Panel C80 User's manual V1.02...
  • Page 53: Vnc Server Configuration For Plc

    It is important to note that the destination port must match the port in the developer tools. 6.2.4 VNC server configuration for PLC VNC must be set under Visualization / Visu mode to use the configuration options in this menu. Power Panel C80 User's manual V1.02...
  • Page 54: Boot Options

    6.3.1 Startup procedure To enter the boot manager of the Power Panel C80, the [Esc], [Del] or [F2] key must be pressed after the USB controller is initialized. If a B&R panel with touch sensor is used during device configuration, Setup can be opened by quickly tapping the upper edge of the touch area.
  • Page 55: Boot Menu

    "Boot manager" on page 55). 6.3.3 Boot manager The boot manager lists all detected and bootable legacy or UEFI media. It is possible to select the media from which the boot procedure should be performed. Power Panel C80 User's manual V1.02...
  • Page 56: Updating/Installing The C80 System

    Updating/Installing with Automation Studio and USB flash drive 1. Create a corresponding project in Automation Studio with the hardware used. 2. Select the desired Automation Runtime, Visual Components, mapp versions, etc. 3. Rebuild/Build the configuration of the project. Power Panel C80 User's manual V1.02...
  • Page 57: Terminal Os (Embedded Linux) System

    There are several ways to find an upgrade package on the website: either on the product page (possible to search for the order number) under Downloads / PPC upgrades or on the Downloads page under Software / Automation Studio / Automation Studio 4.9 (or higher) in section PPC upgrade. Power Panel C80 User's manual V1.02...
  • Page 58 4. After the Power Panel successfully boots, a plausibility check is performed and the update of the terminal OS is started. 5. After a successful update, the system is rebooted and the version of the terminal OS image can be read out in SDM under Terminal. Power Panel C80 User's manual V1.02...
  • Page 59: Viewing License Information

    For technical reasons, the ZIP file may contain files with the same name. This should be taken into account when unpacking the ZIP file. 4. After unpacking, the license files can be viewed in folder ...\licenses. The ZIP file with the license information can also be downloaded from the B&R website (www.br-automation.com). Power Panel C80 User's manual V1.02...
  • Page 60: Network Information

    16 px is set as the default font size. 6.7.2 Supported video formats Videos can be displayed in the HMI application. The following container formats are supported when embedding videos into a web-based HMI application: • WebM • MP4 (H.264) Power Panel C80 User's manual V1.02...
  • Page 61: User Agent

    If DNS is enabled and a hostname is specified for the terminal, the IP address of the terminal can be determined using appropriate network tools (e.g. nslookup). Port The port was configured in the corresponding parameter (default setting: 9222). Power Panel C80 User's manual V1.02...
  • Page 62: Keyboard

    The [?123], [ABC], [1/2] and [2/2] keys can be used to open additional keyboard layouts: " ↵ & ⇐ ▼ ← → € £ ¥ µ § < > ° ↵ ´ ‰ ∑ ∅ ‧ ± ⇐ ▼ ← → Power Panel C80 User's manual V1.02...
  • Page 63: File Formats

    The boot animation is superimposed over an existing static boot logo. The boot animation is only displayed when establishing the connection between the terminal and the HMI application (web application). It is not displayed while the device is booting. Power Panel C80 User's manual V1.02...
  • Page 64: Commissioning

    The mouse cursor automatically appears if a USB mouse is connected to the Power Panel. If the left and right mouse buttons are pressed simultaneously for more than 2 seconds, the Power Panel navigates to the service pages. A USB keyboard is configurable in Automation Studio. Power Panel C80 User's manual V1.02...
  • Page 65: Maintenance

    The self-discharge time when changing the battery is approx. 2 minutes. Required tools • Flat-blade screwdriver Procedure 1. Disconnect the power supply cable to the Power Panel (disconnect the power cable). 2. Carry out electrostatic discharge on the housing or at the ground connection. Power Panel C80 User's manual V1.02...
  • Page 66 7. Reset the date and time in BIOS. ✓ The battery change is completed and the device is ready for operation. Warning! Lithium batteries are hazardous waste! Used batteries must be disposed of in accordance with local regulations. Power Panel C80 User's manual V1.02...
  • Page 67: Cleaning

    • Line type: This can result in permanent damage. What causes image persistence? • Static images • No screensaver • Sharp transitions in contrast (e.g. black/white) • High ambient temperatures • Operation outside of specifications Power Panel C80 User's manual V1.02...
  • Page 68: Repairs/Complaints And Replacement Parts

    Repairs are therefore only permitted to be carried out by authorized qualified personnel at the manufacturer's premises. To process a repair/complaint, a repair order or complaint must be created via the B&R Material Return Portal on the B&R website (www.br-automation.com). Power Panel C80 User's manual V1.02...
  • Page 69: Accessories

    Tightening torque 0.20 to 0.25 Nm 0.22 to 0.25 Nm Electrical properties Nominal voltage 300 V Nominal current The respective limit values of the Power Panel or Panel PC must be taken into account! Power Panel C80 User's manual V1.02...
  • Page 70: 0Tb1210.3100

    Yes, although applies only if all components installed in the complete system have this certification and are listed on the associated DNV GL certificate for the product family. The limit data for each I/O module must be taken into consideration. Power Panel C80 User's manual V1.02...
  • Page 71: Replacement Parts

    Accessories 9.3 Replacement parts The following replacement parts are available for the B&R Power Panel C80. Order number Short description Figure Accessories 5ACCRHMI.0018-000 HMI C80/PPC1200 battery compartment - 1x battery holder C80/PPC1200 - 1x battery including circuit board 9.3.1 5ACCRHMI.0018-000 - Technical data...
  • Page 72: International And National Certifications

    EN 61000-6-4:2007 Electromagnetic compatibility (EMC) - Part 6-4: Generic standards - Emission stan- dard for industrial environments Information: The declarations of conformity are available on the B&R website under Declarations of conformity. Power Panel C80 User's manual V1.02...
  • Page 73: Certifications

    Products with this mark are tested by an accredited test laboratory and certified by the ACMA. The mark is valid for Australia/Oceania and facilitates the certification of your machines and systems in this economic area (based on EU conformity). Power Panel C80 User's manual V1.02...
  • Page 74: Environmentally Friendly Disposal

    Electronics recycling Operating and monitoring devices Uninterruptible power supplies Batteries and rechargeable batteries Cables Paper/Cardboard packaging Paper/Cardboard recycling Plastic packaging material Plastic recycling Disposal must be carried out in accordance with applicable legal regulations. Power Panel C80 User's manual V1.02...