4.6.8 LED status indicators

Assignment
1)
S5: Soft-off
S4: Hibernate (suspend-to-disk)
Automation PC 3100 User's manual V 2.10
LED
Color
Status
(1):
Green
On
Power
Blinking
Red
On
Blinking
Red-Green Blinking
Yellow
On
(2):
Yellow
On
Disk
(3):
Yellow
On
Link
Blinking
(4):
Green
Blinking
Run
Green
On
Red
On
Orange
Blinking
Explanation
Power supply OK
The device is started up; the battery state is BAD.
Information:
For additional information,
page
44.
The system is in power saving mode (standby).
The MTCX is running; the battery state is "BAD". The
system is in power saving mode (standby).
Faulty or incomplete BIOS, MTCX or I/O FPGA update,
battery state OK, power supply OK
Faulty or incomplete BIOS, MTCX or I/O FPGA up-
date, battery state OK, power saving mode (standby)
Faulty or incomplete BIOS, MTCX or I/O FPGA up-
date, battery state BAD, power supply OK
Faulty or incomplete BIOS, MTCX or I/O FPGA up-
date, battery state BAD, power saving mode (stand-
by)
1)
Information:
An update must be performed again.
Power supply not OK. The system is running in UPS
mode.
Indicates drive access (HDD, SSD, CFast)
Indicates an active SDL connection on the panel con-
nector.
An active SDL connection was interrupted due to pow-
er loss of the panel.
Information:
Check the power supply or power connection of the connected panel.
Automation Runtime is starting up.
Controlled by Automation Runtime (ARemb and AR-
win).
Application running
Controlled by Automation Runtime (ARemb and AR-
win).
Application in SERVICE mode
Controlled by Automation Runtime (ARemb and AR-
win).
A license violation has occurred.
Technical data
LED status indicator
500 ms per interval
1
2
see "Battery" on
1)
1)
1)
1
2
43