Determining The Ambient Temperature - B&R Automation PC 3100 User Manual

Hide thumbs Also See for Automation PC 3100:
Table of Contents

Advertisement

Technical data

4.5.1.4 Determining the ambient temperature

1. Select the system unit.
2. The columns specify the maximum or minimum temperature in worst-case operation or the maximum tem-
perature in typical operation of the complete system depending on the respective system unit.
Information:
The maximum and typical temperature specifications correspond to a specification at 500 me-
ters above sea level. The respective ambient temperature is derated approx. 1°C per 1000 meters
starting at 500 m above sea level.
3. If expansion options and CFast cards are additionally installed in the APC3100 system, these components
may result in a temperature limitation.
° If a "✓" (check mark) is entered for the installed component, it can be operated without any prob-
lems.
° If the installed component has a temperature specification (e.g. "45[°C]"), the ambient temperature
of the complete system is not permitted to exceed this value.
4. Possible limitations may arise due to the mounting orientation of the APC3100. For additional information,
see section
"Mounting orientations" on page
5. The relevant test and assessment must be carried out individually by the user on site (reading out the tem-
peratures in BIOS or using the ADI Control Center). See section
page
33.
34
30.
"Information about typical conditions" on
Automation PC 3100 User's manual V 2.10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Apc 3100

Table of Contents