General Technical Data For The Fieldbus Network Adapter - Emerson PACSystems RSTi-EP User Manual

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J
10. Power supply connector for the system and input modules
11. Power supply connector for output modules
12. Service flap
13. Latching hook for latching onto module sides
14. System bus
15. System current path
16. Input current path
17. Type plate with block diagram
18. Output current path
1.3
General Technical Data for the Fieldbus
Network Adapter
Item
Type of connection
Configuration interface
Dimensions
Protection class (DIN EN 60529)
Flammability rating UL 94
Temperature data (Network
Adapter Power Supply)
Humidity
Air pressure
Vibration resistance
Introduction
Description
Spring-style
USB 2.0
Height
Width
Depth
IP 20
V-0
Operation
(horizontal installation)
Operation
(vertical installation)
Storage, transport
Operation
Storage, transport
Operation
Storage, transport
5 Hz ≤ f ≤ 8.4 Hz: 3.5 mm amplitude, per IEC 60068-2-6
8.4 Hz ≤ f ≤ 150 Hz: 1 g acceleration, per IEC 60068-2-6
Single-wired, Fine-wired
Conductor cross-section 0.14 – 1.5 mm
(AWG 16 – 26)
120.0 mm (4.72 in)
(with release lever: 128.0 mm / 5.04 in)
52.0 mm (2.05 in)
76.0 mm (2.99 in)
-20°C to +60°C (- 4 to +140 °F)
(8-A power supply)
-20°C to +55°C (- 4 to +131 °F)
(10-A power supply)
-20°C to +55°C (- 4 to +131 °F)
(6-A power supply)
-20°C to +50°C (- 4 to +122 °F)
(8-A power supply)
-40°C to +85°C (- 40 to +185 °F)
95 %, non-condensing as per IEC 61131-2
95 %, non-condensing as per IEC 61131-2
≥ 795 hPa (altitude ≤ 2,000 m)
per IEC 61131-2
≥ 700 hPa (altitude ≤ 3,000 m)
per IEC 61131‑2
Chapter 1
Oct 2019
2
4

Advertisement

Table of Contents
loading

Table of Contents