Figure 10 Air Cooled Fan Speed Control General Arrangement - Emerson Liebert Challenger 3000 Installation Manual

Precision cooling for business-critical continuity, 3 & 5 tons, 50 & 60hz
Hide thumbs Also See for Liebert Challenger 3000:
Table of Contents

Advertisement

Figure 10 Air cooled fan speed control general arrangement

Traps* every
25 ft. (7.6m)
of rise
Hot Gas
Discharge
Hot Gas
Bypass
Valve
Liquid Return
Solenoid
Valves
Sight
Shutoff *
Glass
Valve
Filter
Drier
Hot Gas
Bypass
Check Valve
(Shipped Loose for
Field Installation)
SINGLE CIRCUIT SHOWN
FACTORY
PIPING
FIELD
PIPING
Condenser
Coil
Schrader
Valve
Fusible
Plug
Inverted Traps* on discharge
and return lines to extend
above base of coil by a
minimum of 7 1/2" (190mm)
Evaporator
Coil
Expansion
Valve
Service
Valves
Scroll
Compressor
*Components are not supplied by Liebert but
are recommended for proper circuit operation
and maintenance.
21
Air Cooled Models
Sensing
Bulb
External
Equalizers
SL-11897 PG 5