Modifiable Parameters EP-3664
Channel
Description
Frequency suppression
0 ... 3
Channel diagnosis
0 ... 3
Diag short circiut 24V
0 ... 3
Diag line break 24V
0 ... 3
Measurement range
Diagnostic Data EP-3664
Name
Error indicator
Module type
Error byte 2
Error byte 3
Detailed Description of I/O Modules
Options
disabled (0) /
50 Hz (1) /
60 Hz (2) /
Average over 16 values (3)
disabled (0) / enabled (1)
disabled (0) / enabled (1)
disabled (0) / enabled (1)
0 to 20 mA (0) /
4 to 20 mA (1) /
0 V to 10 V (2) /
-10 to 10 V (3) /
0 to 5 V (4) /
-5 to 5 V (5) /
1 to 5 V (6) /
2 to 10 V (7) /
disabled (8)
Bytes
Bit
Description
0
Module error
1
Internal error
2
External error
3
Channel error
0
4
Error
5
Power supply fault
6
Reserved
7
Parameter error
0
1
Module Type
2
3
1
4
Channel information available
5
Reserved
6
Reserved
7
Reserved
2
0-7
Reserved
0-2
Reserved
3
3
Internal diagnostic FIFO full
4
Power supply fault
Chapter 5
Oct 2019
Default
disabled
disabled
disabled
disabled
disabled
Default
0
0x05
1
0
0
0
0
0
255