† Internal process data mapping with data format "Standard". Depending on the fieldbus specification and the data
format of the communicating fieldbus components the bytes and/or words can be reversed during data transfer
Measurement Range EP-3664
Measurement
Current (I) /
range
Voltage (U)
21.67 mA
20 mA
0 – 20 mA
10 mA
0 mA
21.67 mA
20 mA
4 – 20 mA
12 mA
4 mA
3.6 mA
10.5V
0 – 10 V
10 V
5 V
Detailed Description of I/O Modules
Bytes
Bit
Description
2
Line break sensor supply
3
Fuse blown
4
Line break signal
5
Reserved
6
Lower limit exceeded
7
Upper limit exceeded
15 - 42
0 - 7
Reserved
43-46
Time stamp [μs] (32-bit)
Description
AI0
AI1
AI2
AI3
Decimal (D)
Hexadecimal
29957
0x7505
27648
0x6C00
13824
0x3600
0
0x0000
29957
0x7505
27648
0x6C00
13824
0x3600
0
0x0000
-691
0XFD4D
29030
0x7166
27648
0x6C00
13824
0x3600
Remarks
Range
Conversion
Overloading
D = 27648 x I / 20
I = D x 20 / 27648
Nominal range
Overloading
D = 27648 x (I – 4) / 16
Nominal range
I=(D x 16 / 27648 )+ 4
Underloading
Overloading
D = 27648 x U/10
I = D x 10 / 27648
Nominal range
Chapter 5
Oct 2019
Default
0
0
257