Modifiable Parameters For Ep-4164; Diagnostic Data Ep-4164 - Emerson PACSystems RSTi-EP User Manual

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J

Modifiable Parameters for EP-4164

Channel
Description
0 - 3
Output range
0 - 3
Substitute value

Diagnostic Data EP-4164

Name
Error indicator
Module type
Error byte 2
Error byte 3
Channel type
Diagnostic bits per
channel
Detailed Description of I/O Modules
Options
0 to 20 mA (0) /
4 to 20 mA (1) /
0 V to 10 V (2) /
-10 to 10 V (3) /
0 to 5 V (4) /
-5 to 5 V (5) /
1 to 5 V (6) /
2 to 10 V (7) /
disabled (8)
Depending on the channels data format (S5/S7
Bytes
Bit
Description
0
Module error
1
Internal error
2
External error
3
Channel error
0
4
Error
5
Reserved
6
Reserved
7
Parameter error
0
1
Module Type
2
3
1
4
Reserved
5
Reserved
6
Reserved
7
Reserved
2
0-7
Reserved
0-2
Reserved
3
Internal diagnostic FIFO full
4
Power supply fault
3
5
Reserved
6
Reserved
7
Reserved
0-6
Channel type
4
7
Reserved
5
Number of diagnostic bit per channel
Chapter 5
Oct 2019
Default
disabled
0
Default
0
0
0
0x05
0
0
0
0
0
0
0
0
0
0x73
0
0
279