Emerson PACSystems RSTi-EP User Manual page 48

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J
Modbus TCP
Network
EPXMBE001
Adapter, 2 Cu
RJ45 Ports,2048
/EPXMBE101
bytes (Input +
Output)
Configuration
IP-Address
#
# In Dual LAN Mode
(EPXMBE101 only)
parameterizable for each
Ethernet Port
Subnet mask
#
# In Dual LAN Mode
(EPXMBE101 only)
parameterizable for each
Ethernet Port
Gateway#
# In Dual LAN Mode
(EPXMBE101 only)
parameterizable for each
Ethernet Port
#
IP Configuration
# In Dual LAN Mode
(EPXMBE101 only)
parameterizable for each
Ethernet Port
Modbus Dual LAN Mode
(EPXMBE101 only)
Modbus DHCP Timeout
IP-Address USB-Port
Webserver via Ethernet
Save module parameters
Status Modbus watchdog
Modbus Connection
Timeout
Writing access with
multiclient
Check reference list before
exchanging data
Process alarm
Diagnostic alarm
Behavior of outputs on
fieldbus error
4 numbers between 0-255
4 numbers between 0-255
4 numbers between 0-255
Static,
DHCP,
BootP
Firmware 02.00.00 and higher:
additionally DHCP and static
disabled / enabled
Waiting time,
1 to 1,000 s
192.168.1.202;
192.168.2.202,
192.168.3.202,
192.168.4.202, 192.168.5.202
disabled / enabled
no / yes / Standard
Watchdog time in steps of
10ms
Connection watchdog time in
sec
write for all, 1stWr1stServe,
1stConn1stServe
disabled / enabled
disabled / enabled
disabled / enabled
All outputs off /
Enable substitute values /
Hold last value
Chapter 3
Oct 2019
192.168.0.222
255.255.255.0
192.168.0.1
Static (firmware
01.xx.xx)
DHCP and static
(firmware
02.00.00 or
higher)
disabled
30 s
192.168.1.202
enabled
no, see register
0x113C-0x113F
0 *10ms,
see register
0x1120
1 s,
see register
0x1131
write for all,
see register
0x1130
disabled,
see register
0x1132
disabled,
see register
0x1133
disabled,
see register
0x1134
All outputs off,
see register
0x1135
33