Process Data
Byte
Format
QB0
Word
QB1
QB2
Word
QB3
QB4
Word
QB5
QB6
Word
QB7
†
Internal process data mapping with data format Standard. Depending on the fieldbus specification and the data
format of the communicating fieldbus components the bytes and/or words can be reversed during data transfer
Value Range† EP-4264
Measurement
Current (I) /
range
Voltage (U)
21.67 mA
20 mA
0 – 20 mA
10 mA
0 mA
21.67 mA
20 mA
4 – 20 mA
12 mA
4 mA
3.6 mA
10.5V
10 V
0 – 10 V
5 V
0 V
+10.5V
10 V
5 V
±10 V
0 V
-5 V
-10 V
-10.5V
+10.5V
10 V
2 - 10 V
6 V
2 V
Detailed Description of I/O Modules
†
Outputs EP-4264
Description
AO0
AO1
AO2
AO3
Decimal (D)
Hexadecimal
29957
0x7505
27648
0x6C00
13824
0x3600
0
0x0000
29957
0x7505
27648
0x6C00
13824
0x3600
0
0x0000
-691
0XFD4D
29030
0x7166
27648
0x6C00
13824
0x3600
0
0x0000
29030
0x7166
27648
0x6C00
13824
0x3600
0
0x0000
-13824
0xCA00
-27648
0x9400
-29030
8E9A
29376
0x72C0
27648
0x6C00
13824
0x3600
0
0x0000
Remarks
Range
Conversion
Overloading
D = 27648 x I / 20
I = D x 20 / 27648
Nominal range
Overloading
D = 27648 x (I – 4) / 16
Nominal range
I=( D x 16 / 27648 )+ 4
Underloading
Overloading
D = 27648 x U/10
I = D x 10 / 27648
Nominal range
Overloading
D = 27648 x U / 10
Nominal range
U = D x 10 / 27648
Underloading
Overloading
D = 27648 x (U – 2) / 8
U = D x 8 / 27648 + 2
Nominal range
Chapter 5
Oct 2019