Process Data † Outputs Ep-4264; Value Range† Ep-4264 - Emerson PACSystems RSTi-EP User Manual

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J
Process Data
Byte
Format
QB0
Word
QB1
QB2
Word
QB3
QB4
Word
QB5
QB6
Word
QB7
Internal process data mapping with data format Standard. Depending on the fieldbus specification and the data
format of the communicating fieldbus components the bytes and/or words can be reversed during data transfer
Value Range† EP-4264
Measurement
Current (I) /
range
Voltage (U)
21.67 mA
20 mA
0 – 20 mA
10 mA
0 mA
21.67 mA
20 mA
4 – 20 mA
12 mA
4 mA
3.6 mA
10.5V
10 V
0 – 10 V
5 V
0 V
+10.5V
10 V
5 V
±10 V
0 V
-5 V
-10 V
-10.5V
+10.5V
10 V
2 - 10 V
6 V
2 V
Detailed Description of I/O Modules
Outputs EP-4264
Description
AO0
AO1
AO2
AO3
Decimal (D)
Hexadecimal
29957
0x7505
27648
0x6C00
13824
0x3600
0
0x0000
29957
0x7505
27648
0x6C00
13824
0x3600
0
0x0000
-691
0XFD4D
29030
0x7166
27648
0x6C00
13824
0x3600
0
0x0000
29030
0x7166
27648
0x6C00
13824
0x3600
0
0x0000
-13824
0xCA00
-27648
0x9400
-29030
8E9A
29376
0x72C0
27648
0x6C00
13824
0x3600
0
0x0000
Remarks
Range
Conversion
Overloading
D = 27648 x I / 20
I = D x 20 / 27648
Nominal range
Overloading
D = 27648 x (I – 4) / 16
Nominal range
I=( D x 16 / 27648 )+ 4
Underloading
Overloading
D = 27648 x U/10
I = D x 10 / 27648
Nominal range
Overloading
D = 27648 x U / 10
Nominal range
U = D x 10 / 27648
Underloading
Overloading
D = 27648 x (U – 2) / 8
U = D x 8 / 27648 + 2
Nominal range
Chapter 5
Oct 2019
287

Advertisement

Table of Contents
loading

Table of Contents