Specifications Ep-5311; Modifiable Parameters For Ep-5311 - Emerson PACSystems RSTi-EP User Manual

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J

Specifications EP-5311

Specification
System data
Data
Interface
System bus transfer rate
Number of channels
Type
SSI transfer rate
Delay time
Data width
Data format
SSI mode
Sensor supply
Reverse polarity protection
Module diagnosis
Individual channel diagnosis
Cable length
Supply
Supply voltage
Current consumption from system current path
ISYS,
Current consumption from input current path IIN
General data
Weight
For additional general data, refer to Section 1.5,
General Technical Data for I/O Modules.

Modifiable Parameters for EP-5311

Channel
Description
0
Delay time
7
Values in brackets for Modbus-TCP and EtherCAT.
Detailed Description of I/O Modules
Description
Process, parameter and diagnostic data depend on the network
Adapter used (refer to Chapter 3.1, Order and Arrangement of
Modules).
RSTi-EP I/O communication bus
48 Mbps
1
SSI (Differential RS422)
125 kHz ... 2 MHz
1μs ... 64μs
8- ... 32-bit
Binary /
Gray-Code
Listening /
Master
500 mA (24Vdc) /
400 mA (5Vdc)
Yes
Yes
No
max. 320 m (1049.9 ft) at 125 kHz; shielded
20.4V – 28.8V
8 mA
25 mA + sensor supply current
87 g (3.07 oz)
Options
7
1μs (0) /
2μs (1) /
4μs (2) /
8μs (3) /
16μs (4) /
32μs (5) /
Chapter 5
Oct 2019
Default
64μs
226

Advertisement

Table of Contents
loading