User Manual
GFK-2958J
Name
Channel 2 error
Channel 4 error
to
Channel 31 error
Time stamp
Process Data† Inputs EP-3264
Byte
IB0
IB1
IB2
IB3
IB4
IB5
IB6
IB7
†
Internal process data mapping with data format "Standard". Depending on the fieldbus
specification and the data format of the communicating fieldbus components the bytes and/or
words can be reversed during data transfer
Measurement Range EP-3264
Measurement
Current (I) /
range
Voltage (U)
21.67 mA
20 mA
0 – 20 mA
10 mA
0 mA
21.67 mA
20 mA
4 – 20 mA
12 mA
4 mA
3.6 mA
Detailed Description of I/O Modules
Bytes
Bit
7
0
1
2
3
14
4
5
6
7
15 - 42
0 - 7
43-46
Format
Word
Word
Word
Word
Decimal (D)
Hexadecimal
29957
0x7505
27648
0x6C00
13824
0x3600
0
0x0000
29957
0x7505
27648
0x6C00
13824
0x3600
0
0x0000
-691
0XFD4D
Description
Upper limit exceeded
Parameter Error
Overload
Line break sensor supply
Fuse blown
Line break signal
Reserved
Lower limit exceeded
Upper limit exceeded
Reserved
Time stamp [μs] (32-bit)
Description
Remarks
AI0
AI1
AI2
AI3
Range
Overloading
Nominal range
Overloading
Nominal range
Underloading
Chapter 5
Oct 2019
Default
0
0
Conversion
D = 27648 x I / 20
I = D x 20 / 27648
D = 27648 x (I – 4) / 16
I=( D x 16 / 27648 )+ 4
250