Process Data† Inputs Ep-3264; Measurement Range Ep-3264 - Emerson PACSystems RSTi-EP User Manual

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J
Name
Channel 2 error
Channel 4 error
to
Channel 31 error
Time stamp
Process Data† Inputs EP-3264
Byte
IB0
IB1
IB2
IB3
IB4
IB5
IB6
IB7
Internal process data mapping with data format "Standard". Depending on the fieldbus
specification and the data format of the communicating fieldbus components the bytes and/or
words can be reversed during data transfer

Measurement Range EP-3264

Measurement
Current (I) /
range
Voltage (U)
21.67 mA
20 mA
0 – 20 mA
10 mA
0 mA
21.67 mA
20 mA
4 – 20 mA
12 mA
4 mA
3.6 mA
Detailed Description of I/O Modules
Bytes
Bit
7
0
1
2
3
14
4
5
6
7
15 - 42
0 - 7
43-46
Format
Word
Word
Word
Word
Decimal (D)
Hexadecimal
29957
0x7505
27648
0x6C00
13824
0x3600
0
0x0000
29957
0x7505
27648
0x6C00
13824
0x3600
0
0x0000
-691
0XFD4D
Description
Upper limit exceeded
Parameter Error
Overload
Line break sensor supply
Fuse blown
Line break signal
Reserved
Lower limit exceeded
Upper limit exceeded
Reserved
Time stamp [μs] (32-bit)
Description
Remarks
AI0
AI1
AI2
AI3
Range
Overloading
Nominal range
Overloading
Nominal range
Underloading
Chapter 5
Oct 2019
Default
0
0
Conversion
D = 27648 x I / 20
I = D x 20 / 27648
D = 27648 x (I – 4) / 16
I=( D x 16 / 27648 )+ 4
250