Modifiable Parameters For Epxetc001; Rsti-Ep Status Messages - Emerson PACSystems RSTi-EP User Manual

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J
Storage temperature
Air humidity (operation/transport)
Width
Depth
Height
Weight
Configuration

Modifiable Parameters for EPXETC001

Parameter
IP address USB port
Process alarm
Diagnostic
Behavior of outputs on fieldbus
error
Module behavior on hot swap
Data format
Webserver via Ethernet
Coupler control
Change requires restart of the network adapter.

RSTi-EP Status Messages

In addition to the process input data a network adapter status word as well as module
status bytes are transferred to the SPS. Thus, diagnostics and status messages can be read
directly.
The network adapter status word describes the status of the RSTi-EP station including the
following information:
Network Adapter Status Bits EPXETC001
Bit
Name
Summarized module
0
diagnosis
1
Errorbit 1
2
Errorbit 2
3
System bus error
4
Errorbit 4
Detailed Descriptions of the Fieldbus Network Adapters
-40°C to +85°C (-40 °F to +185 °F)
5% to 95%, noncondensing as per IEC 61131-2
52 mm (2.05 in)
76 mm (2.99 in)
120 mm (4.72 in)
227 g (8 oz)
ESI
https://www.emerson.com/Industrial-Automation-
Controls/support
which supports EtherCAT. The ESI supporting a firmware release is
part of the firmware upgrade kit, also available on the Support
website.
Optional values
192.168.1.202; 192.168.2.202, 192.168.3.202,
192.168.4.202,
192.168.5.202
disabled / enabled
disabled / enabled
All outputs off /
Enable substitute value/
Hold last value
Continue data exchange /
Behavior like fieldbus error
Motorola / Intel
disabled / enabled / enabled
Reserved
Description
Module diagnostic is present. A diagnosis is available for at least one module with
diagnostics functionality.
Reserve bit 1, currently not used
Reserve bit 2, currently not used
Error on the system bus. Communication with the connected modules is disrupted.
Reserve bit 4, currently not used
file
is
available
on
for download and import into Programmer Tool
Chapter 4
Oct 2019
the
Support
website
Default
192.168.1.202
disabled
disabled
All outputs off
Continue data exchange
Motorola
disabled / enabled
Off
72

Advertisement

Table of Contents
loading