Specifications EP-2218

Specification
System data
Data
Interface
System bus transfer rate
Outputs
Number
Type of load
Response time
Max. output current
Breaking energy (inductive)
Switching frequency
Actuator connection
Short-circuit-proof
Protective circuit
Response time of the current limiting circuit
Module diagnosis
Individual channel diagnosis
Reactionless
Supply
Supply voltage
Current consumption from system current path
ISYS
Current consumption from output current path
IOUT
General data
Weight
For additional general data, refer to Section 1.5,
General Technical Data for I/O Modules.

Modifiable Parameters for EP-2218

Channel
0 - 7
Detailed Description of I/O Modules
Description
Process, parameter and diagnostic data depend on the network
adapter used (refer to Chapter 3.1, Order and Arrangement of
Modules).
RSTi-EP I/O communication bus
48 Mbps
8
ohmic, inductive, lamp load
low » high max. 100μs; high » low max. 250μs
per channel
per module
150 mJ per channel
Resistive load (min. 47Ω)
Inductive load (DC 13)
Lamp load (12 W)
2-wire
Yes
Constant current with thermal switch-off and automatic restart
< 100μs
Yes
No
Yes
20.4V – 28.8V
8 mA
35 mA + load
86 g (3.03 oz)
Description
Substitute value
0.5 A
4 A
1 kHz
0.2 Hz without free-wheeling diode
1 kHz with suitable free-wheeling
diode
1 kHz
Options
Off (0) / On (1)
Chapter 5
Oct 2019
Default
Off (0)
142