Emerson PACSystems RSTi-EP User Manual page 427

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J
1.1
4.2
4.3
EP-1902
Status LED
EP-1922
LED Indicators and Troubleshooting
Interruption in one of the two safety
loops of a safety circuit for at least 3
seconds.
Cross connection between the safety
loops for at least 3 seconds.
Off: Safety circuit 1 interrupted
Yellow: Safety circuit 1 OK
Off: OSSD not active
Yellow: OSSD active, 24Vdc at output
Green: Feed-in voltage in valid range
Red:
Module has not been snapped properly
Error in the supply voltage
Channel error
Overload at the OSSD output level
External feed-in recognized from field
side
Internal error detected
Interruption in one of the two safety
loops of a safety circuit for at least 3
seconds.
Cross connection between the safety
loops for at least 3 seconds.
Check safety circuit for
interruptions if an interruption of
the safety channel is not part of
the application.
Check safety circuit for cross
connections.
Check safety circuit 1
Check that the module has been
snapped into place properly
Check the supply voltage
check +24 V input current path
Check voltage on plug 4.3; in
case of cascading 0 V might be
properly, therefore this is not an
error
Check channel error
– Remove cross connection at
OSSD
Measure voltage at OSSD pin
(4.3) vs. GND (4.4).
If a voltage is present, check the
wiring.
Attention: safety hazard! Shut
down the system and prevent it
from switching on again.
Module might have switched off
caused by overtemperature;
check the temperature inside the
switch cabinet
Perform a cold start within 24
hours
If the error has not been fixed,
send the module to Emersonfor a
technical examination.
Check safety circuit for
interruptions if an interruption of
the safety channel is not part of
the application.
Check safety circuit for cross
connections.
Chapter 12
Oct 2019
412