Measurement Range EP-3368

Measurement
Current (I) /
range
Voltage (U)
0 – 20 mA
21.67 mA
20 mA
10 mA
0 mA
4 – 20 mA
21.67 mA
20 mA
12 mA
4 mA
3.6 mA
The following applies for all ranges:
input value > overload range = 0x7FFF
input value < underload range = 0x8000
5.28

Analog Input Module EP-3468

Figure 160: Analog Input
Module EP-3468
Detailed Description of I/O Modules
Decimal
Hexadecimal
(D)
29957
0x7505
27648
0x6C00
13824
0x3600
0
0x0000
29957
0x7505
27648
0x6C00
13824
0x3600
0
0x0000
-691
0XFD4D
Range
Conversion
Overloading
D = 27648 x I / 20
I = D x 20 / 27648
Nominal range
Overloading
D = 27648 x (I – 4) / 16
I=( D x 16 / 27648 )+ 4
Nominal range
Underloading
Figure 161: Connection Diagram EP-3468
-