Process Data Inputs Ep-5311; Digital Pulse Width Modulation Output Module Ep-5422 - Emerson PACSystems RSTi-EP User Manual

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J

Process Data Inputs EP-5311

Byte
IB0
IB1
IB2
IB3
IB4
IB5
Internal process data mapping with data format "Standard". Depending on the fieldbus specification
and the data format of the communicating fieldbus components the bytes and/or the words can be
reversed during the data transfer. For byte/word order for each fieldbus coupler refer to Section 3.10.
5.21
Digital Pulse Width Modulation Output Module
EP-5422
Figure 138: Digital Pulse Width
Modulation Output Module
EP-5422
The digital pulse width modulation module EP-5422 is used for the control of small motors
with current requirements of up to 0.5 A. The period duration for each channel can be
parameterized from 25μs to approx. 175ms (input values from 1,202 to 8,388,607 based
on a factor 0.02083μs).
Via an output double word in the process data the pulse duration is defined from 0μs to
approx. 175ms for each channel (input values from 0 to 8,388,607 based on a factor
0.02083μs). If the pulse duration is equal or exceeds the duration of the period, the output
is set permanently.
Detailed Description of I/O Modules
Format
Double word
Word
Figure 139: Connection Diagram EP-5422
Chapter 5
Description
Encoder Value
16 Bit Time Stamp
Oct 2019
229