Measurement
Current (I) /
range
Voltage (U)
1.8V
5.25V
5 V
1 - 5 V
3 V
1 V
0.9 V
5.25 V
5 V
0 – 5 V
2.5 V
0 V
5.25 V
5 V
2.5 V
±5 V
0 V
-2.5 V
-5 V
-5.25 V
† If the process value is beyond the valid value range, the corresponding channel releases 0 V and 0 mA respectively
The following applies for all ranges:
value > overload range = output deactivated
value < underload range = output deactivated
Detailed Description of I/O Modules
Decimal (D)
Hexadecimal
-691
0XFD4D
29376
0x72C0
27648
0x6C00
13824
0x3600
0
0x0000
-691
0XFD4D
29030
0x7166
27648
0x6C00
13824
0x3600
0
0x0000
29376
0x72C0
27648
0x6C00
13824
0x3600
0
0x0000
-13824
0xCA00
-27648
0x9400
-43200
0x5740
Range
Conversion
Underloading
Overloading
D = 27648 x (U – 1) / 4
Nominal range
U = (D x 4 / 27648) + 1
Underloading
Overloading
D = 27648 x U/5
I = D x 5 / 27648
Nominal range
Overloading
D = 27648 x (U – 1) / 4
Nominal range
U = (D x 4 / 27648) + 1
Underloading