LED Indicators EPXPBS001
For error messages, refer to Chapter 12, LED Indicators and Troubleshooting.

Addressing

The network adapter on the PROFIBUS-DP is addressed via the two rotary switches.
Note:
Coding: Address = (H*16) + L
Figure 19: Rotary Switch Default Setting EPXPBS001: Address = 3
Detailed Descriptions of the Fieldbus Network Adapters
LED
EPXPBS001
Green: Supply voltage > 18Vdc
Power Supply
Red: At least one current path < 18 V
3.1
Green: Input current path supply voltage > 18Vdc
3.2
Red: Input current path supply voltage < 18Vdc
3.3
3.4
Red: Internal fuse defective
4.1
Green: Output current path supply voltage > 18Vdc
4.2
Red: Output current path supply voltage < 18Vdc
4.3
4.4
Red: Internal fuse defective
A maximum of 125 addresses (1 to 125) can be assigned. Each address may be assigned
only once in the overall bus structure. Addresses 1 and 2 are generally used by the control
systems.
Bus
addresses
The most significant digit is set with rotary switch H, the least significant digit with rotary
switch L. The switches are labelled in the hexadecimal numbering system (0 to 9, A=10,
B=11, C=12, ... F = 15). A hexadecimal to decimal conversion table is provided in the annex.
000
plus
126
and
higher
Chapter 4
Oct 2019
may
not
be
used.