Additional Counter Features - Emerson PACSystems RSTi-EP User Manual

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J
Counting Range
Limits
End value
Lower count limit
Periodic Counting/ Primary Direction Down
Figure 101: Periodic Counting, Primary Counting Direction Down
5.16.9.1.1
Counting Range
Limits
End value
Upper count limit

Additional Counter Features

You can define the additional features for the counter listed below by parameterizing or via
the process data outputs:
Detailed Description of I/O Modules
process alarm will be triggered if it is parameterized. All status bits remain set until
they are reset with the bit Reset status bits in the control word.
Valid range of values
–2 147 483 647 (–2
+2 147 483 648 (2
Down-counting starts at the load value.
If the parameterized end value +1 is reached during counting in the negative
direction, the counter jumps back to the load value at the next count pulse and
continues counting from there. The status bit End value reached is set and a process
alarm will be triggered if it is parameterized.
Upon reaching the upper count limit the counter jumps to the lower count limit to
continue counting from there. The status bit Overflow performed is set and a
process alarm will be triggered if it is parameterized. All status bits remain set until
they are reset with the bit Reset status bits in the control word.
Reset: resets the counting value to the load value during counting.
Latch function: stores the current counting value in the latch register.
31
+ 1) to +2 147 483 647 (2
31
)
Valid range of values
–2 147 483 647 (–2
31
) to +2 147 483 646 (2
+2 147 483 648 (2
31
-1)
Chapter 5
Oct 2019
31
– 1)
31
– 2)
178

Advertisement

Table of Contents
loading

Table of Contents