Emerson PACSystems RSTi-EP User Manual page 425

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J
Status LED
EP-3804
EP-3704
Channel LED
1.1-4.1
Analog output modules
Status LED
EP-4164
EP-4264
Channel LED
1.1-4.1
Power modules
EP-7631
Status LED
3.2
3.4
EP-7641
Status LED
LED Indicators and Troubleshooting
Red:
Error in supply voltage at input current
path
Communication error on the system bus
There is a new diagnostic message
Channel error
Firmware error
Status LED off and all other LEDs red: Error in
the bus network adapter power supply
Red:
Input signal outside permissible range
Line break
Cold-junction compensation error (EP-
3804 only)
System bus cannot be accessed (for
example, caused by interruption of the
bus network adapter power supply)
Red:
Error in supply voltage
Communication error
Channel error
Status LED off and all other LEDs red: Error in
the bus network adapter power supply
Red:
Overload in voltage mode
Broken line in current mode
System bus cannot be accessed (for
example, caused by interruption of the
bus network adapter power supply)
Red:
– Channel error or communication error on the
system bus, or there is an error in the supply
voltage
Red:
Supply voltage of the feed in plug < 18Vdc
Red:
Damage of internal fuse
Red:
Check that the module has been
snapped into place properly
Check the supply voltage
Check channel error
Check firmware, update firmware
as necessary
Check the bus network adapter
supply voltage
Check the input signal, the
cabling and, if necessary, the
sensor for external cold-junction
compensation.
Check the bus network adapter
supply voltage
Check that the module has been
snapped into place properly
Check the supply voltage
Check the channel error
– Check the bus network adapter
supply voltage
Check the connected load, check
the cabling,
Check the bus network adapter
supply voltage
Check that the module has been
snapped into place properly
Check the channel error, check
the supply voltage
Check supply voltage of feed in
plug
Replace module
Check that the module has been
snapped into place properly
Chapter 12
Oct 2019
410

Advertisement

Table of Contents
loading

Table of Contents