0X1010 Process Image Length In Bits For The Output Modules; 0X1010 Process Image Length In Bits For The Input Modules; 0X1017 Register - Mapping Revision; 0X1018 - 0X101B Collective Diagnostics Message For I/O Modules - Emerson PACSystems RSTi-EP User Manual

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J
7
Master configuration error
8
Errorbit 8
9
Errorbit 9
10
Force mode active
11
Errorbit 11
12
Errorbit 12
13
Voltage UOUT error
14
Voltage UIN error
15
Errorbit 15
0x1010 Process Image Length in Bits for the Output
Modules
0x1010 Process Image Length in Bits for the Input
Modules
0x1017 Register – Mapping Revision
Version of the register structure
0x1018 – 0x101B Collective Diagnostics Message for I/O
Modules
If a diagnostic alarm is activated (register 0x1134) and there is a diagnostic message for a
module, it is indicated here with a set bit. A module's slot position corresponds to its
position in the 64-bit data field (minus passive modules without slot recognition). Example:
0x0000 0000 0000 0002 = There is a diagnostic alarm for module 2.
Reading the module's diagnostic memory (0xAXXX) confirms the diagnosis and resets the
corresponding bit. In case of multiple diagnoses for one module, only the most up-to-date
diagnosis is displayed. The next diagnostic is then placed in a wait loop and only becomes
active once the current one has been confirmed.
Detailed Descriptions of the Fieldbus Network Adapters
Master configuration error. The list of configured modules (reference module list
0x2800 – 0x287F) differs significantly from the module list detected by the
network adapter (current module list 0x2A00 – 0x2A7F). Process data cannot be
exchanged with the modules.
Reserve bit 8, currently not used
Reserve bit 9, currently not used
Force mode was activated via the web server.
Forced channels do not exchange data with the master.
Reserve bit 11, currently not used
Reserve bit 12, currently not used
Error in the supply voltage of outputs
Error in the supply voltage of system and inputs
Reserve bit 15, currently not used