GFK-2958J
Diagnostic Update
Delay
Maximum Active
Alarms
Slave Functions
Extra Alarm Service
Access Point
Configuration Data
Convention
Enabled Alarms
Pull Plug Alarm
Process Alarm
Diagnostic Alarm
Manufacture Alarm
Status Alarm
Update Alarm
Commissioning
The maximum number of extra diagnosis cycles that the master waits
to obtain from a slave the release for a DATA_EXCHANGE. If the
Diagnostic Update Delay is set to 0, the master waits for one
diagnosis cycle before reporting an error. If the Diagnostic Update
Delay is set to 15, the master waits for 16 diagnosis cycles before
reporting an error. The master waits for one diagnosis cycle more
than the value of the Diagnostic Update Delay.
Some newer slave devices require more time for the consistency
testing for the processing of the SET_PRM parameterizing telegrams.
Therefore, a simple diagnosis cycle may be insufficient until the
participant can inform the Master of the release for the
DATA_EXCHANGE.
Valid range: 0 through 15.
The maximum number of possible active alarms.
Choices:
1 alarm of each type
2, 4, 8, 12, 16, 24 or 32 alarms in total
The service access point (SAP) through which the master quits
alarms.
Choices:
Master Alarm acknowledge SAP51: Master quits alarms via
SAP51.
Master Alarm acknowledge SAP50: Master quits alarms via
SAP50.
The DPV1 data types.
Choices:
Configuration Data of EN 50170
Configuration Data of DPV1
Modifiable or read-only, depending on the GSD file. When this box is
checked, a slot signals the withdrawal of a module or the insertion of
a module.
Modifiable or read-only, depending on the GSD file. When this check
box is checked, a process alarm signals the occurrence of an event in
the connected process. For example, the event may be "upper limit
value exceeded."
Modifiable or read-only, depending on the GSD file. When this check
box is checked, a diagnostic alarm signals an event within a slot. For
example, events may be over temperature or short circuit.
Modifiable or read-only, depending on the GSD file. When this box is
checked, manufacturer-specific alarms are enabled.
Modifiable or read-only, depending on the GSD file. When this check
box is checked, a status alarm signals a change in the state (such as
run, stop, or ready) of a module.
Modifiable or read-only, depending on the GSD file. When this check
box is checked, an update alarm signals the change of a parameter in
a slot, for example, by a local operation or remote access.
Chapter 8