0X1000 - 0X1006 Network Adapter Identifier; 0X1000 - 0X1006 Network Adapter Status - Emerson PACSystems RSTi-EP User Manual

Remote i/o system
Hide thumbs Also See for PACSystems RSTi-EP:
Table of Contents

Advertisement

User Manual
GFK-2958J
Module
EP-225F
EP-2814
EP-2714
EP-291F
EP-5111
EP-5112
EP-5212
EP-5422
EP-5442
EP-3164
EP-3264
EP-3664
EP-3124
EP-3804
EP-3368
EP-3468
EP-4164
EP-4264
EP-3704
EP-1901
EP-1922
EP-1902
0x1000 – 0x1006 Network Adapter Identifier
The identifier is the product designation: EPXMBE001 and EPXMBE101 as per Network
adaptor Catalog number.
0x1000 – 0x1006 Network Adapter Status
Bit
Name
Summarized module
0
diagnosis
1
Errorbit 1
2
Errorbit 2
3
System bus error
4
Errorbit 4
5
Errorbit 5
6
I/O-Configuration error
Detailed Descriptions of the Fieldbus Network Adapters
Process data
Input
--
--
--
--
2 DWord, 2 Word
2 DWord, 2 Word
4 DWord, 2 Word
2 Word
2 Word
4 Word
4 Word
4 Word
4 Word
4 Word
8 Word
8 Word
--
--
4 Word
4 Byte
4 Byte
Byte
Meaning
A diagnosis is available on at least one module with diagnostics functionality.
Reserve bit 1, currently not used
Reserve bit 2, currently not used
Error on system bus. Communication with the connected modules is disrupted.
Reserve bit 4, currently not used
Reserve bit 5, currently not used
Differing configuration. The module list has changed. The list of configured
modules (reference module list 0x2800 – 0x287F) differs from the module list
detected by the network adapter (current module list 0x2A00 – 0x2A7F).
Output
2 Byte
1 Byte
1 Byte
2 Byte
2 DWord, 1 Word
2 DWord, 2 Word
2 DWord, 2 Word
2 DWord, 2 Word
2 DWord, 2 Word
--
--
--
--
--
--
--
4 Word
4 Word
--
--
--
--
Chapter 4
Oct 2019
88

Advertisement