Selection of operation mode and operation location

4.18 Selection of operation mode and operation location

Purpose
Operation mode selection
Started in Network operation mode
Selection of operation location

4.18.1 Operation mode selection (Pr. 79)

Used to select the operation mode of the inverter.
Mode can be changed as desired among operation using external command signals (External operation), operation
from the operation panel and PU (FR-PU07/FR-PU04) (PU operation), combined operation of PU operation and
External operation (External/PU combined operation), and Network operation (when RS-485 communication is used).
Parameter
Name
Number
Operation
79
mode
selection
This parameter allows its setting to be changed in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter write selection.
∗ The priorities of the frequency commands when Pr. 79 = "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog input (AU)
> digital input from the operation panel".
166
Operation mode selection
Operation mode at power-on
Operation command source and
speed command source during
communication operation, selection
of operation location
Initial
Setting
Value
Range
Use External/PU switchover mode (
0
PU and External operation mode.
At power ON, the inverter is in the External operation mode.
1
Fixed to PU operation mode
Fixed to External operation mode
2
Operation can be performed by switching between the external
and NET operation mode.
External/PU combined operation mode 1
Frequency command
Operation panel and PU (FR-
PU04/FR-PU07) setting or
3
0
external signal input (multi-speed
setting, across terminals 4-5 (valid
when AU signal turns ON)). ∗
External/PU combined operation mode 2
Frequency command
External signal input
4
(terminal 2, 4, JOG, multi-speed
selection, etc.)
Switchover mode
6
Switchover among PU operation, External operation, and NET
operation is available while keeping the same operation status.
External operation mode (PU operation interlock)
X12 signal ON
Operation mode can be switched to the PU operation mode.
7
(output stop during External operation)
X12 signal OFF
Operation mode can not be switched to the PU operation mode.
Parameter that should be Set
Description
) to switch between the
Start command
External signal input
(terminal STF, STR)
Start command
Enter from
panel and
PU (FR-PU04/FR-PU07)
Refer to Page
Pr. 79
Pr. 79, Pr. 340
Pr. 338, Pr. 339
Pr. 551
LED Indication
PU operation mode
External operation
mode
NET operation mode
PU operation mode
External operation
mode
NET operation mode
External/PU
combined operation
mode
of the operation
and
of the
PU operation mode
External operation
mode
NET operation mode
166
174
175
:OFF
:ON