Reference Of The Terminal Ca (Analog Current Output) And Am (Analog Voltage Output) (Pr. 55, Pr. 56, Pr. 866, Pr. 867, Pr. 869) - Mitsubishi Electric FR-A740-00023 Instruction Manual

Fr-a700 series
Table of Contents

Advertisement

4.16.3 Reference of the terminal CA (analog current output) and AM (analog voltage
output) (Pr. 55, Pr. 56, Pr. 866, Pr. 867, Pr. 869)
Two types of monitor output, analog current output from the terminal CA and analog voltage output from the
terminal AM, are available.
Set the reference of the signal output from terminal CA and AM.
Parameter
Name
Number
Frequency monitoring
55 *
reference
Current monitoring
56 *
reference
Torque monitoring
866 *
reference
867
AM output filter
869
Current output filter
* The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr.
77 Parameter write selection.
(1) Frequency monitoring reference (Pr. 55)
(10VDC)
(20mADC)
1Hz
50Hz
(initial value)
Setting range of Pr. 55
(2) Current monitoring reference (Pr. 56)
(10VDC)
(20mADC)
Rated current
(initial value)
Setting range of Pr. 56
Initial
Setting Range
Value
50Hz
0 to 400Hz
01800
0 to
Rated
or less
500A
inverter
02160
0 to
current
or more
3600A
150%
0 to 400%
0.01s
0 to 5s
0.02s
0 to 5s
• Set the frequency to be referenced when the frequency monitor
(output frequency/set frequency) is selected for the terminal CA and
terminal AM display.
• Set the frequency when the current output at terminal CA is
20mADC.
The analog current output and inverter output frequency at terminal
CA are proportional. (The maximum output current is 20mADC.)
• Set the frequency (output frequency/set frequency) when the voltage
400Hz
output at terminal AM is 10VDC.
The analog voltage output and frequency at terminal AM are
proportional. (The maximum output voltage is 10VDC.)
• Set the current to be referenced when the current monitor (inverter
output current, etc.) is selected for the terminal CA and terminal AM
display.
• Set the current value when the current output at terminal CA is
20mADC.
The analog current output and current value at terminal CA are
proportional. (The maximum output current is 20mADC.)
• Set the current value when the voltage output at terminal AM is
500A
10VDC.
(3600A)
The analog voltage output and current value at terminal AM are
proportional. (The maximum output voltage is 10VDC.)
Monitor display and monitor output signal
Description
Set the full-scale value to output the output frequency
monitor value to terminal CA and AM.
Set the full-scale value to output the output current
monitor value to terminal CA and AM.
Set the full-scale value to output the torque monitor value
to terminal CA and AM.
Set the output filter of terminal AM.
Adjust response level of current output.
4
249