Object 0Xf100; Object 0Xf200; Table 33: Structure For Object 0Xf100; Table 34: Structure Of Object 0Xf200 - WAGO I/O-SYSTEM 750 Manual

Ethercat fieldbus coupler, id switch 100 mbit/s; digital and analog signals
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-354/000-001 EtherCAT® Fieldbus Coupler, ID Switch
7.3.1.3

Object 0xF100

Object 0xF100 contains the status data of the fieldbus coupler according to the
modular device profile. In addition, it contains the diagnostic messages for the I/O
modules.
The following table presents the structure of object 0xF100.

Table 33: Structure for Object 0xF100

Sub-Index Data Type
0
1
2
3
4
5
7.3.1.4

Object 0xF200

Object 0xF200 contains the control data for the fieldbus coupler according to the
modular device profile. In addition, it contains the control word for the I/O module
diagnostic messages.
The following table presents the structure of object 0xF200.

Table 34: Structure of Object 0xF200

Sub-Index Data Type
0
1
2
3
4
5
UINT8
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
UINT16
UINT8
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
UINT16
Function Description
Number of bits
8
1
1
1
1
16
Number of bits
8
1
1
1
1
16
Description
Number of Entries
K-Bus Cycle Overrun
Flag
Input Process Data Hold
Acknowledge
Output Process Data
Hold Acknowledge
Output Process Data
Clear Acknowledge
Diagnostics Status Word
Description
Number of Entries
K-Bus Cycle Overrun
Flag Disable
Input Process Data Hold
Request
Output Process Data
Hold Request
Output Process Data
Clear Request
Diagnostics Control Word
Manual
Version 1.2.1
75

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-354/000-001

Table of Contents