WAGO-I/O-SYSTEM 750
750-354/000-001 EtherCAT® Fieldbus Coupler, ID Switch
11.2.5.14 EnOcean Radio Receiver
750-642
The EnOcean radio receiver has a total of 4 bytes of user data in both the Input
and Output Process Image (3 bytes of module data and 1 byte of control/status).
The following tables illustrate the Input and Output Process Image, which have 2
words mapped into each image. Word alignment is applied.
Table 170: EnOcean Radio Receiver 750-642
Input Process Image
Offset
0
1
Output Process Image
Offset
0
1
11.2.5.15 MP Bus Master Module
750-643
The MP Bus Master Module has a total of 8 bytes of user data in both the Input
and Output Process Image (6 bytes of module data and 2 bytes of control/status).
The following table illustrates the Input and Output Process Image, which have 4
words mapped into each image. Word alignment is applied.
Table 171: MP Bus Master Module 750-643
Input and Output Process Image
Offset
0
1
2
3
Byte Destination
High Byte
D0
D2
Byte Destination
High Byte
-
-
Byte Destination
High Byte
C1/S1
D1
D3
D5
Low Byte
S
Data byte
D1
Low Byte
C
not used
-
Low Byte
Extended
C0/S0
Control/
Status byte
D0
D2
D4
I/O Modules 183
Description
Status byte
Data bytes
Description
Control byte
not used
Description
Control/status
byte
Data bytes
Manual