Table 71: Object 0X7020 (Output Data 750-504); Table 72: Object 0X1603 (Rxpdo 750-504); Table 73: Object 0X7030 (Output Data 750-550); Table 74: Object 0X1602 (Rxpdo 750-550) - WAGO I/O-SYSTEM 750 Manual

Ethercat fieldbus coupler, id switch 100 mbit/s; digital and analog signals
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-354/000-001 EtherCAT® Fieldbus Coupler, ID Switch
I/O Module Objects 750-504 (4 DO)
For the third I/O module (4 DO, 750-504) in the fieldbus node, the following
objects are created.

Table 71: Object 0x7020 (Output Data 750-504)

Subindex
0
1
2
3
4

Table 72: Object 0x1603 (RxPDO 750-504)

Subindex
0
1
2
3
4
I/O Module Objects 750-550 (2 AO)
For the fourth I/O module (2 AO, 750-550) in the fieldbus node, the following
objects are created.

Table 73: Object 0x7030 (Output Data 750-550)

Subindex
0
1
2

Table 74: Object 0x1602 (RxPDO 750-550)

Subindex
0
1
2
Data Type
Number of Bits
UINT8
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Data Type Description
UINT8
Number of Entries
UINT32
Output Mapping Area 1
UINT32
Output Mapping Area 2
UINT32
Output Mapping Area 3
UINT32
Output Mapping Area 4
Data Type
Number of Bits
UINT8
UINT16
UINT16
Data Type Description
UINT8
Number of Entries
UINT32
Output Mapping Area 1
UINT32
Output Mapping Area 2
Function Description
Description
8
Number of Entries
1
Channel 1, Data
1
Channel 2, Data
1
Channel 3, Data
1
Channel 4, Data
Value
4
0x7020.01.01
0x7020.02.01
0x7020.03.01
0x7020.04.01
Description
8
Number of Entries
16
Channel 1, Word 1
16
Channel 2, Word 1
Value
2
0x7030.01.10
0x7030.02.10
93
Manual
Version 1.2.1

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-354/000-001

Table of Contents