Behavior During Other Operating Errors; Configuration Error In A Sync Manager - WAGO I/O-SYSTEM 750 Manual

Ethercat fieldbus coupler, id switch 100 mbit/s; digital and analog signals
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-354/000-001 EtherCAT® Fieldbus Coupler, ID Switch
If the local bus is not running, a status change from PREOP to SAFEOP is not
possible.
If the fieldbus coupler is in PREOP, SAFEOP, or OP states, an EMCY message
is sent using the LED blink code assigned to local bus error.
Additional information about EMCY messages
You can read about the EMCY messages in more detail in the appendix,
"EMCY Codes" chapter.
Additional Information about the LED blink codes
You can read about the LED blink codes in more detail in the "Diagnostics"
chapter,  "Fieldbus Coupler Diagnostics"  "Node Status Evaluation –
I/O LED (Blink Code Table)".
9.4

Behavior during Other Operating Errors

During regular operation, the following errors can occur during certain
circumstances:
Incorrect configuration of a Sync Manager by the EtherCAT
Interruption of the cyclical process data exchange
Error in CoE access
9.4.1

Configuration Error in a Sync Manager

Configuration errors in one of the Sync Managers can occur during status change
from INIT to PREOP or from PREOP to SAFEOP. These lead to a denial of the
requested status change by the corresponding AL status code.
Additional information about AL status codes!
A list of the AL status codes and their meanings can be found in the appendix,
"AL Status Codes" chapter.
The settings of Sync Managers 0 and 1 (mailbox) are checked during status
change from INIT to PREOP.
The master extracts the settings either from the SII (slave's EEPROM) or from
the optional XML file with the device description of the EtherCAT
Diagnostics 135
®
master
®
fieldbus
Manual
Version 1.2.1