WAGO-I/O-SYSTEM 750
750-354/000-001 EtherCAT® Fieldbus Coupler, ID Switch
6.3

Connecting a Conductor to the CAGE CLAMP

The WAGO CAGE CLAMP
finely stranded conductors.
Only connect one conductor to each CAGE CLAMP
Only one conductor may be connected to each CAGE CLAMP
Do not connect more than one conductor at one single connection!
If more than one conductor must be routed to one connection, these must be
connected in an up-circuit wiring assembly, for example using WAGO feed-
through terminals.
1.
For opening the CAGE CLAMP
above the connection.
2.
Insert the conductor into the corresponding connection opening.
3.
For closing the CAGE CLAMP
now clamped firmly in place.

Figure 35: Connecting a Conductor to a CAGE CLAMP

®
connection is appropriate for solid, stranded and
®
insert the actuating tool into the opening
®
simply remove the tool. The conductor is
®
Connect Devices
®
®
!
®
.
Manual
Version 1.2.1
65