System Description
Fieldbus coupler or controller
Internal system supply module
Input current I
Activate all outputs when testing the current consumption!
If the electrical consumption of a power supply point for the 24 V system
supply exceeds 500 mA, then the cause may be an improperly
dimensioned node or a defect.
During the test, you must activate all outputs.
3.5.4

Field Supply

3.5.4.1

Connection

Sensors and actuators can be directly connected to the relevant channel of the
I/O module in 1, 2, 3 or 4 conductor connection technology. The I/O module
supplies power to the sensors and actuators. The input and output drivers of
some I/O modules require the field side supply voltage.
The power supply modules provide field side power (24 VDC). In this case it is a
passive power supply without protection equipment. Power supply modules are
available for different potentials, e.g. 24 VDC, 230 VAC or others.
Power supply modules with or without fuse holder and diagnostic capability are
available for the power supply of other field potentials (24 VDC,
0 ... 230 VAC/DC, 120 VAC, 230 VAC). The power supply modules can also be
used to set up various potential groups. The connections are connected in pairs
to a power contact.
Manual
Version 1.2.1
750-354/000-001 EtherCAT® Fieldbus Coupler, ID Switch
I
= Sum of all the internal current consumption of the
(5 V) total
connected I/O modules + internal current consumption of
the fieldbus coupler/controller
I
= Sum of all the internal current consumption of the
(5 V) total
connected I/O modules at internal system supply module
5 V
=
×
(24 V)
24 V
η = Efficiency of the power supply at nominal load 24 V
WAGO-I/O-SYSTEM 750
I
(5 V) total
η