Table 179: Description Of Marking Example According To Atex And Iecex - WAGO I/O-SYSTEM 750 Manual

Ethercat fieldbus coupler, id switch 100 mbit/s; digital and analog signals
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-354/000-001 EtherCAT® Fieldbus Coupler, ID Switch

Table 179: Description of Marking Example According to ATEX and IECEx

Marking
TUEV 07 ATEX 554086 X
IECEx TUN 09.0001 X
Dust
II
3 D
Ex
tc
IIIC
T135°C
Dc
Mining
I
M2
Ex
d
I
Mb
Gases
II
3 G
Ex
nA
IIC
T4
Gc
Use in Hazardous Environments 191
Description
Approving authority resp. certificate numbers
Equipment group: All except mining
Category 3 (Zone 22)
Explosion protection mark
Type of protection: Protection by enclosure
Explosion group of dust
Max. surface temperature of the enclosure
(without a dust layer)
Equipment protection level (EPL)
Equipment group: Mining
Category: High level of protection
Explosion protection mark
Type of protection: Flameproof enclosure
Explosion group for electrical equipment for
mines susceptible to firedamp
Equipment protection level (EPL)
Equipment group: All except mining
Category 3 (Zone 2)
Explosion protection mark
Type of protection: Non-sparking equipment
Explosion group of gas and vapours
Temperature class: Max. surface temperature
135 °C
Equipment protection level (EPL)
Manual
Version 1.2.1

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-354/000-001

Table of Contents