WAGO-I/O-SYSTEM 750
750-354/000-001 EtherCAT® Fieldbus Coupler, ID Switch
3.5

Power Supply

3.5.1

Overcurrent Protection

The system and field voltage of the WAGO-I/O-SYSTEMs 750 is supplied on the
head stations and bus supply modules.
For components that work with extra low voltage, only SELV/PELV voltage
sources should be used.
A single voltage source supplying multiple components must be designed
according to the component with the strictest electrical safety requirements.
For components which are only allowed to be supplied by SELV voltage sources,
these requirements are listed in the technical data.
Most components in the WAGO-I/O-SYSTEM 750 have no internal overcurrent
protection. Therefore, appropriate overcurrent production must always be
implemented externally for the power supply to these components, e.g. via fuses.
The maximum permissible current is listed in the technical data of the
components used.
3.5.2

Isolation

Within the fieldbus node, there are three electrically isolated potentials:
Electrically isolated fieldbus interface via transformer
Electronics of the fieldbus couplers/controllers and the I/O modules (local
bus)
All I/O modules have an electrical isolation between the electronics (local
bus, logic) and the field electronics. Some digital and analog input modules
have each channel electrically isolated, please see catalog.